05000373/FIN-2015002-01: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by StriderTol)
 
(Created page by program invented by StriderTol)
 
Line 12: Line 12:
| identified by = NRC
| identified by = NRC
| Inspection procedure = IP 71111.12
| Inspection procedure = IP 71111.12
| Inspector = J Cassidy, J Robbins, M Kunowski, M Learn, R Ruiz, R Zuffa, S Winters, V Myersa, Dunlop C, Hunt D, Chyu D, Krause J, Robbins M, Holmberg M, Kunowski R, Ruiz R, Zuff
| Inspector = J Cassidy, J Robbins, M Kunowski, M Learn, R Ruiz, R Zuffa, S Winters, V Myersa, Dunlopc Hunt, D Chyu, D Krause, J Robbins, M Holmberg, M Kunowski, R Ruiz, R Zuffa
| CCA = N/A for ROP
| CCA = N/A for ROP
| INPO aspect =  
| INPO aspect =  
| description = (Opened) Unresolved Item 05000374/2015002-01: Both Ammonia Detectors Non-Functional on Unit 0 Train A of Control Room Ventilation. The inspectors identified an unresolved item (URI) concerning the failure of both Unit 0 Train A (0A) control room ventilation ammonia detectors. These detectors were previously removed from the TSs by amendment.  On June 26, licensee staff identified that both ammonia detectors in the 0A Train of control room ventilation were non-functional. The inspectors identified that Amendments 61 and 42 contained language referencing these detectors. The amendments indicated that a commitment was made with respect to maintenance of these detectors. The licensee maintains a listing of current commitments, but this item was not on that list. The actual commitment predated the implementation of the licensees formal commitment tracking program. The particulars of the commitment were contained in referenced correspondence. A review of the correspondence will allow the inspectors to determine if additional regulatory action is warranted. This issue has been entered into the CAP under AR 2520223, NRC Question on Ammonia Detector Commitment. This issue is a URI pending NRC evaluation of the details found in the correspondence referenced above (URI 05000373/2015002-01, Both Ammonia Detectors Non-Functional on Unit 0 Train A of Control Room Ventilation).
| description = (Opened) Unresolved Item 05000374/2015002-01: Both Ammonia Detectors Non-Functional on Unit 0 Train A of Control Room Ventilation. The inspectors identified an unresolved item (URI) concerning the failure of both Unit 0 Train A (0A) control room ventilation ammonia detectors. These detectors were previously removed from the TSs by amendment.  On June 26, licensee staff identified that both ammonia detectors in the 0A Train of control room ventilation were non-functional. The inspectors identified that Amendments 61 and 42 contained language referencing these detectors. The amendments indicated that a commitment was made with respect to maintenance of these detectors. The licensee maintains a listing of current commitments, but this item was not on that list. The actual commitment predated the implementation of the licensees formal commitment tracking program. The particulars of the commitment were contained in referenced correspondence. A review of the correspondence will allow the inspectors to determine if additional regulatory action is warranted. This issue has been entered into the CAP under AR 2520223, NRC Question on Ammonia Detector Commitment. This issue is a URI pending NRC evaluation of the details found in the correspondence referenced above (URI 05000373/2015002-01, Both Ammonia Detectors Non-Functional on Unit 0 Train A of Control Room Ventilation).
}}
}}

Latest revision as of 19:53, 20 February 2018

01
Site: LaSalle Constellation icon.png
Report IR 05000373/2015002 Section 1R12
Date counted Jun 30, 2015 (2015Q2)
Type: URI:
cornerstone Mitigating Systems
Identified by: NRC identified
Inspection Procedure: IP 71111.12
Inspectors (proximate) J Cassidy
J Robbins
M Kunowski
M Learn
R Ruiz
R Zuffa
S Winters
V Myersa
Dunlopc Hunt
D Chyu
D Krause
J Robbins
M Holmberg
M Kunowski
R Ruiz
R Zuffa
INPO aspect
'