| event date = 10/28/2018 00:00 CDT
| event date = 10/28/2018 00:00 CDT
| last update date = 10/28/2018
| last update date = 10/28/2018
| title =  
| title = Automatic Reactor Scram During a Reactor Shutdown
| event text =  
| event text = At 0445 [CDT], with reactor power less than 1% rated thermal power on Instrument Range Monitor (IRM) ranges 6 and 7, Clinton Power Station received an automatic Reactor Protection System (RPS) actuation. The Reactor Scram Off Normal procedure was entered and all control rods were verified to be fully inserted. The apparent cause of the scram is cold water injection causing an upscale trip of the IRMs due to Motor Driven Reactor Feedwater Pump (MDRFP) Feedwater Regulating valve 1FW004 valve coming off the full shut seat momentarily. All systems responded appropriately following the scram and the plant is currently stable.  Clinton Power Station will be proceeding to Mode 4 to support the planned Maintenance Outage.
The NRC Senior Resident Inspector has been notified.
| URL = https://www.nrc.gov/reading-rm/doc-collections/event-status/event/2018/20181029en.html#en53698
| URL = https://www.nrc.gov/reading-rm/doc-collections/event-status/event/2018/20181029en.html#en53698
}}{{unit info
}}{{unit info

Latest revision as of 01:00, 24 February 2020

ENS 53698 +/-
Where
Clinton Constellation icon.png
Illinois (NRC Region 3)
Reporting
10 CFR 50.72(b)(2)(iv)(B), RPS Actuation
Time - Person (Reporting Time:+3.95 h0.165 days <br />0.0235 weeks <br />0.00541 months <br />)
Opened: David Livingston
08:57 Oct 28, 2018
NRC Officer: Mark Abramovitz
Last Updated: Oct 28, 2018
53698 - NRC Website