ENS 52777
From kanterella
Jump to navigation
Jump to search
ENS Event | |
|---|---|
01:38 May 31, 2017 | |
| Title | Automatic Reactor Scram |
| Event Description | At 2038 [CDT], Clinton Power Station received an automatic RPS [Reactor Protection System]actuation. EOP-1 [Emergency Operating Procedure] was entered on RPV [Reactor Pressure Vessel] Level 3. The cause of the scram is unknown at this time. All systems responded appropriately following the scram and the plant is currently stable.
Reactor level is being maintained by normal feedwater and decay heat is being removed to the main condenser via the steam dump bypass valves. The plant is in a normal shutdown electrical lineup. The plant main generator was synchronized to the electrical grid and the plant was conducting control rod scram time testing at the time of the reactor trip. The licensee notified the NRC Resident Inspector. |
| Where | |
|---|---|
| Clinton Illinois (NRC Region 3) | |
| Reporting | |
| 10 CFR 50.72(b)(2)(iv)(B), RPS Actuation | |
| Time - Person (Reporting Time:+-3.27 h-0.136 days <br />-0.0195 weeks <br />-0.00448 months <br />) | |
| Opened: | Glenn Benjamin 22:22 May 30, 2017 |
| NRC Officer: | Jeff Rotton |
| Last Updated: | May 30, 2017 |
| 52777 - NRC Website
Loading map... | |
Unit 1 | |
|---|---|
| Reactor critical | Critical |
| Scram | A/R |
| Before | Power Operation (28 %) |
| After | Hot Shutdown (0 %) |
WEEKMONTHYEARENS 580022025-10-22T20:35:00022 October 2025 20:35:00
[Table view]10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Manual Reactor Scram ENS 579672025-10-06T08:21:0006 October 2025 08:21:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Automatic Reactor Scram ENS 563282023-02-01T05:43:0001 February 2023 05:43:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Automatic Scram Due to Turbine Trip ENS 541972019-08-03T07:26:0003 August 2019 07:26:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(3)(iv)(A), System Actuation, 10 CFR 50.72(b)(2)(iv)(A), System Actuation - ECCS Discharge En Revision Imported Date 8/7/2019 ENS 536982018-10-28T05:00:00028 October 2018 05:00:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Automatic Reactor Scram During a Reactor Shutdown ENS 531102017-12-09T19:48:0009 December 2017 19:48:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition, 10 CFR 50.72(b)(3)(v)(C), Loss of Safety Function - Release of Radioactive Material Manual Reactor Scram Due to Loss of Division 1 Ac Power to Numerous Components ENS 528002017-06-11T03:56:00011 June 2017 03:56:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Manual Reactor Scram Due to Loss of Feedwater Heating ENS 527772017-05-31T01:38:00031 May 2017 01:38:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Automatic Reactor Scram ENS 499582014-03-26T00:42:00026 March 2014 00:42:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Manual Reactor Scram Due to Loss of Condenser Vacuum ENS 496322013-12-13T23:57:00013 December 2013 23:57:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Manual Reactor Trip During Feed Pump Swap ENS 496172013-12-09T02:27:0009 December 2013 02:27:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(3)(v)(C), Loss of Safety Function - Release of Radioactive Material Manual Scram Due to Loss of Division 1 480 Vac Power Causing Loss of Instrument Air to Containment and Scram Air Header ENS 489742013-04-26T13:55:00026 April 2013 13:55:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Manual Reactor Scram Due to Rapidly Decreasing Level in the Ehc Oil Reservoir ENS 488122013-03-07T13:56:0007 March 2013 13:56:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Automatic Reactor Scram on Generator Trip/Turbine Trip ENS 474892011-11-29T23:28:00029 November 2011 23:28:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Unit Experienced an Automatic Reactor Scram During a Planned Shutdown ENS 454332009-10-15T10:37:00015 October 2009 10:37:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Manual Reactor Scram Due to Reactor Recirculation Pump Trip ENS 439762008-02-11T04:07:00011 February 2008 04:07:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Manual Reactor Scram Due to Increasing Reactor Vessel Level ENS 428072006-08-27T22:05:00027 August 2006 22:05:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Reactor Trip Due to Reactor High Water Level ENS 424302006-03-20T10:53:00020 March 2006 10:53:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Main Turbine Trip Caused Reactor Scram ENS 408682004-07-13T21:10:00013 July 2004 21:10:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Automatic Reactor Scram Due to Possible Adverse Weather ENS 406042004-03-23T01:31:00023 March 2004 01:31:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Reactor Scram from 93% Power Due to Generator Trip ENS 403682003-12-02T22:58:0002 December 2003 22:58:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Scram Due to Low Reactor Water Feed Pump Suction Pressure 2025-10-06T08:21:00 | |
Retrieved from "https://kanterella.com/w/index.php?title=ENS_52777&oldid=102783"