| title = Loss of the Safety Parameter Display System Due to Inverter 2Y-26 Inverter Failure
| title = Loss of the Safety Parameter Display System Due to Inverter Failure
| event text = On May 19, 2019, at 1809 [CDT], the Safety Parameter Display System (SPDS) was lost to both Arkansas Nuclear One Units 1 and 2 due to the SPDS Inverter (2Y-26) failure.  The SPDS Inverter is the power supply to both units' SPDS.  The Unit 2 Control Room dispatched operators in response to a smoke alarm received from the 2Y-26 Inverter room.  Upon arrival, smoke was reported emanating from 2Y-26.  There was no report of fire at any time.  Field operators de-energized 2Y-26 and the smoke ceased.  The loss of SPDS also caused the Power Operating Limits (POL) function of the Unit 2 Core Operating Limits Supervisory System (COLSS) to be lost, so Unit 2 reduced power to 91 [percent] in accordance with Technical Specifications.  Both units are at power and stable.
| event text = On May 19, 2019, at 1809 CDT, the Safety Parameter Display System (SPDS) was lost to both Arkansas Nuclear One Units 1 and 2 due to the SPDS Inverter (2Y-26) failure.  The SPDS Inverter is the power supply to both units' SPDS.  The Unit 2 Control Room dispatched operators in response to a smoke alarm received from the 2Y-26 Inverter room.  Upon arrival, smoke was reported emanating from 2Y-26.  There was no report of fire at any time.  Field operators de-energized 2Y-26 and the smoke ceased.  The loss of SPDS also caused the Power Operating Limits (POL) function of the Unit 2 Core Operating Limits Supervisory System (COLSS) to be lost, so Unit 2 reduced power to 91 [percent] in accordance with Technical Specifications.  Both units are at power and stable.
The NRC Resident has been notified.
The NRC Resident has been notified.
This is reportable per 10CFR50.72(b)(3)(xiii)."
This is reportable per 10 CFR 50.72(b)(3)(xiii).
| URL = https://www.nrc.gov/reading-rm/doc-collections/event-status/event/2019/20190520en.html#en54073
| URL = https://www.nrc.gov/reading-rm/doc-collections/event-status/event/2019/20190521en.html#en54073
}}{{unit info
}}{{unit info
| Unit =  1  
| Unit =  1  

Latest revision as of 23:49, 23 February 2020

ENS 54073 +/-
Where
Arkansas Nuclear Entergy icon.png
Arkansas (NRC Region 4)
Reporting
10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness
Time - Person (Reporting Time:+0.88 h0.0367 days <br />0.00524 weeks <br />0.00121 months <br />)
Opened: Kevin Parks
00:02 May 20, 2019
NRC Officer: Jeff Herrera
Last Updated: May 20, 2019
54073 - NRC Website
Loading map...