ENS 42238: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by Mark Hawes)
 
(Created page by program invented by StriderTol)
 
(One intermediate revision by the same user not shown)
Line 3: Line 3:
| facility = Paducah Gaseous Diffusion Plant
| facility = Paducah Gaseous Diffusion Plant
| Organization =  
| Organization =  
| license number = Gdp-1
| license number = GDP-1
| region = 2
| region = 2
| state = Kentucky
| state = Kentucky
Line 16: Line 16:
| event date = 01/02/2006 04:38 CST
| event date = 01/02/2006 04:38 CST
| last update date = 01/18/2006
| last update date = 01/18/2006
| title = Report Of Safety Equipment Failure
| title = Report of Safety Equipment Failure
| event text = At 0453 CST on 01/02/2006, the Plant Shift Superintendent (PSS) was notified that steam was observed leaking from the C-337A Position 1 West Autoclave.  A 14 ton cylinder containing 0.711 % U235 assay uranium hexafluoride had been heating (TSR [Technical Safety Requirement] Mode 5) for approximately 5 minutes when the leak was observed.  The autoclave pressure containment boundary is a TSR system required to be operable per TSR 2.2.3.1, 'Autoclave High Pressure Isolation System (HPIS),' when the autoclave is in Mode 5.  The autoclave was placed in Mode 2, 'Autoclave Out-of-Service' in accordance with LCO Required Actions 2.2.3.1.C.
| event text = At 0453 CST on 01/02/2006, the Plant Shift Superintendent (PSS) was notified that steam was observed leaking from the C-337A Position 1 West Autoclave.  A 14 ton cylinder containing 0.711 % U235 assay uranium hexafluoride had been heating (TSR [Technical Safety Requirement] Mode 5) for approximately 5 minutes when the leak was observed.  The autoclave pressure containment boundary is a TSR system required to be operable per TSR 2.2.3.1, 'Autoclave High Pressure Isolation System (HPIS),' when the autoclave is in Mode 5.  The autoclave was placed in Mode 2, 'Autoclave Out-of-Service' in accordance with LCO Required Actions 2.2.3.1.C.
This event is reportable as a 24 hour event in accordance with 10CFR 76.120(c)(2)(i).  This is an event in which equipment is disabled or fails to function as designed when: a.) the equipment is required by a TSR to prevent releases, prevent exposures to radiation and radioactive materials exceeding specified limits, mitigate the consequences of an accident, or restore this facility to a pre-established safe condition after an accident; b.) the equipment is required by a TSR to be available and operable and either should have been operating or should have operated on demand, and c.) no redundant equipment is available and operable to perform the required safety function.
This event is reportable as a 24 hour event in accordance with 10CFR 76.120(c)(2)(i).  This is an event in which equipment is disabled or fails to function as designed when: a.) the equipment is required by a TSR to prevent releases, prevent exposures to radiation and radioactive materials exceeding specified limits, mitigate the consequences of an accident, or restore this facility to a pre-established safe condition after an accident; b.) the equipment is required by a TSR to be available and operable and either should have been operating or should have operated on demand, and c.) no redundant equipment is available and operable to perform the required safety function.

Latest revision as of 19:36, 24 November 2018

ENS 42238 +/-
Where
Paducah Gaseous Diffusion Plant
Paducah, Kentucky (NRC Region 2)
License number: GDP-1
Reporting
10 CFR 76.120(c)(2)
Time - Person (Reporting Time:+7.33 h0.305 days <br />0.0436 weeks <br />0.01 months <br />)
Opened: Steven Skaggs
17:58 Jan 2, 2006
NRC Officer: Bill Huffman
Last Updated: Jan 18, 2006
42238 - NRC Website