| event date = 10/28/2018 00:00 EDT
| event date = 10/28/2018 00:00 EDT
| last update date = 10/28/2018
| last update date = 10/28/2018
| title =  
| title = Non Essential Service Water Inoperable
| event text =  
| event text = During the performance of Service Water Essential header swap, SWN-6 (Supply to Turbine Building Oil Coolers) valve stem became disconnected from its gear box at 85% open and could not be operated. Therefore, the non-essential service water system was inoperable. LCO 3.0.3 was entered at 0930 [EDT] with required actions to be in Mode 3 in 7 hours, Mode 4 in 13 hours and Mode 5 in 37 hours. Repair efforts were successful at shutting SWN-6, and LCO 3.0.3 was exited at 1305 [EDT] before adding any negative reactivity in support of shutdown. ('TS Required S/D' box not checked.)
This condition constituted a loss of safety function which requires an 8 hour report [in accordance with] IAW 50.72(b)(3)(v)(B): Without the ability to close SWN-6, the non-seismic portion of the conventional Service Water System could not be isolated as required in the event of either a seismic event or as required in the EOPs. The nonessential service water system is required to support the recirculation phase post [Design Basis Accident] DBA for accident mitigation.
The licensee notified the NRC Resident Inspector and the State of New York.
| URL = https://www.nrc.gov/reading-rm/doc-collections/event-status/event/2018/20181029en.html#en53699
| URL = https://www.nrc.gov/reading-rm/doc-collections/event-status/event/2018/20181029en.html#en53699
}}{{unit info
}}{{unit info

Latest revision as of 13:17, 30 October 2018

ENS 53699 +/-
Where
Indian Point Entergy icon.png
New York (NRC Region 1)
Reporting
10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident

10 CFR 50.72(b)(3)(v)(B), Loss of Safety Function - Remove Residual Heat
Time - Person (Reporting Time:+11.17 h0.465 days <br />0.0665 weeks <br />0.0153 months <br />)
Opened: Michael Weeden
15:10 Oct 28, 2018
NRC Officer: Karen Cotton
Last Updated: Oct 28, 2018
53699 - NRC Website