| title = | | title = Automatic Reactor Scram During a Reactor Shutdown | ||
| event text = | | event text = At 0445 [CDT], with reactor power less than 1% rated thermal power on Instrument Range Monitor (IRM) ranges 6 and 7, Clinton Power Station received an automatic Reactor Protection System (RPS) actuation. The Reactor Scram Off Normal procedure was entered and all control rods were verified to be fully inserted. The apparent cause of the scram is cold water injection causing an upscale trip of the IRMs due to Motor Driven Reactor Feedwater Pump (MDRFP) Feedwater Regulating valve 1FW004 valve coming off the full shut seat momentarily. All systems responded appropriately following the scram and the plant is currently stable. Clinton Power Station will be proceeding to Mode 4 to support the planned Maintenance Outage. | ||
The NRC Senior Resident Inspector has been notified." | |||
| URL = https://www.nrc.gov/reading-rm/doc-collections/event-status/event/2018/20181029en.html#en53698 | | URL = https://www.nrc.gov/reading-rm/doc-collections/event-status/event/2018/20181029en.html#en53698 | ||
}}{{unit info | }}{{unit info |
Revision as of 13:17, 30 October 2018
Where | |
---|---|
Clinton ![]() Illinois (NRC Region 3) | |
Reporting | |
10 CFR 50.72(b)(2)(iv)(B), RPS Actuation | |
Time - Person (Reporting Time:+3.95 h0.165 days <br />0.0235 weeks <br />0.00541 months <br />) | |
Opened: | David Livingston 08:57 Oct 28, 2018 |
NRC Officer: | Mark Abramovitz |
Last Updated: | Oct 28, 2018 |
53698 - NRC Website
| |