ENS 53696: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by StriderTol)
(Created page by program invented by StriderTol)
 
(3 intermediate revisions by the same user not shown)
Line 9: Line 9:
| unit = 1
| unit = 1
| utype = W-2-LP
| utype = W-2-LP
| cfr =  
| cfr = 10 CFR 50.72(b)(3)(iv)(A), 10 CFR 50.72(b)(3)(xiii)
| emergency class =  Non Emergency  
| emergency class =  Non Emergency  
| notification date = 10/27/2018 01:50
| notification date = 10/27/2018 01:50
Line 16: Line 16:
| event date = 10/26/2018 00:00 EDT
| event date = 10/26/2018 00:00 EDT
| last update date = 10/27/2018
| last update date = 10/27/2018
| title =  
| title = Automatic Start of the Emergency Diesel Generator and Loss of Radiation Monitor
| event text =  
| event text = RCS [Reactor Coolant System] Pressure: vented to containment, refueling cavity greater than 23ft. [above reactor vessel]. RCS temperature: 96 degrees Fahrenheit.
The 12A bus de-energized, 'A' EDG [Emergency Diesel Generator] automatically started and loaded on [emergency] buses 14 and 18. The RCS configuration is refueling cavity level greater than 23ft. above the reactor flange with no impact to shutdown cooling.
Radiation monitor R-1, Control Room radiation monitor, lost power for 2 hrs 10 min. This placed Ginna in a major loss of emergency preparedness capabilities. A temporary radiation monitor has been installed in the Control Room.
Prior to the notification, the licensee had restored the 12A bus from offsite power and the R-1 monitor was re-energized.
The licensee notified the NRC Resident Inspector.
| URL = https://www.nrc.gov/reading-rm/doc-collections/event-status/event/2018/20181029en.html#en53696
| URL = https://www.nrc.gov/reading-rm/doc-collections/event-status/event/2018/20181029en.html#en53696
}}{{unit info
}}{{unit info

Latest revision as of 13:17, 30 October 2018

ENS 53696 +/-
Where
Ginna Constellation icon.png
New York (NRC Region 1)
Reporting
10 CFR 50.72(b)(3)(iv)(A), System Actuation

10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness
Time - Person (Reporting Time:+21.83 h0.91 days <br />0.13 weeks <br />0.0299 months <br />)
Opened: Wade Weber
01:50 Oct 27, 2018
NRC Officer: Ossy Font
Last Updated: Oct 27, 2018
53696 - NRC Website
Loading map...