05000352/FIN-2018001-02: Difference between revisions
Jump to navigation
Jump to search
StriderTol (talk | contribs) (Created page by program invented by StriderTol) |
StriderTol (talk | contribs) (Created page by program invented by StriderTol) |
||
(One intermediate revision by the same user not shown) | |||
Line 5: | Line 5: | ||
| finding integer = 02 | | finding integer = 02 | ||
| quarter = 2018Q1 | | quarter = 2018Q1 | ||
| IR section = | | IR section = 4OA3 | ||
| finding type = NCV | | finding type = NCV | ||
| significance = | | significance = Green | ||
| cornerstone = Mitigating Systems | | cornerstone = Mitigating Systems | ||
| violation of = Technical Specification | | violation of = Technical Specification | ||
| identified by = Self-Revealing | | identified by = Self-Revealing | ||
| Inspection procedure = IP | | Inspection procedure = IP 71153 | ||
| Inspector = | | Inspector = S Rutenkroger, M Fannon, H Anagnostopoulos, J Furia, J Krafty | ||
| CCA = | | CCA = | ||
| INPO aspect = | | INPO aspect = PI.3 | ||
| description = A self-revealed Green NCV of LGS Unit 1 TS 6.8.1 and TS 3.8.1.1 was identified when Exelon failed to properly maintain an operating procedure to maintain a fail-safe design feature for the EDGs which led to the D12 EDG combustion air overheating and caused the EDG to be inoperable for greater than its TS allowed outage time. | | description = A self-revealed Green NCV of LGS Unit 1 TS 6.8.1 and TS 3.8.1.1 was identified when Exelon failed to properly maintain an operating procedure to maintain a fail-safe design feature for the EDGs which led to the D12 EDG combustion air overheating and caused the EDG to be inoperable for greater than its TS allowed outage time. | ||
}} | }} |
Latest revision as of 18:34, 10 September 2018
Site: | Limerick |
---|---|
Report | IR 05000352/2018001 Section 4OA3 |
Date counted | Mar 31, 2018 (2018Q1) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | Self-revealing |
Inspection Procedure: | IP 71153 |
Inspectors (proximate) | S Rutenkroger M Fannon H Anagnostopoulos J Furia J Krafty |
Violation of: | Technical Specification |
INPO aspect | PI.3 |
' | |