Aiiieren Callaway Plant MISSOURi March 18, 2021 ULNRC-06630 U.S. Nuclear Regulatory Commission AUn: Document Control Desk Washington, DC 20555-000 1 10 CFR 50.55a Ladies and Gentlemen:

DOCKET NUMBER 50-483 CALLAWAY PLANT UNIT 1 UNION ELECTRIC CO.

RENEWED FACILITY OPERATING LICENSE NPF-30 OWNERS ACTIVITY REPORTS (OAR-i FORMS) FOR CYCLE/REFUEL 24 Please find enclosed the Owners Activity Reports (OAR-i forms) for Cycle 24 and Refuel 24 activities at Callaway Plant. The reports are submitted pursuant to the provisions ofthe applicable revisions ofASME Boiler and Pressure Vessel Code Case N-532, Alternative Requirements to Repair and Replacement Documentation Requirements and Inservice Summary Report Preparation and Submission.

The OAR-f forms enclosed are associated with the following Cycle 24 and Refuel 24 activities at Callaway Plant:

1.

Inservice Inspection (151) and Repair/Replacement activities for the second period of the fourth 151 Program interval, and 2.

Containment Inservice Inspection pursuant to ASME Section XI, subsection IWE for the first period of the third IWE Program interval.

Each enclosed OAR-i form includes a listing of items with identified flaws or relevant conditions that required evaluation for continued service (Table 1) and an abstract of repair/replacement activities required for continued service (Table 2).

In accordance with Revision 1 ofthe Fourth Interval 151 Program Plan, the OAR-i form for the 151 and Repair/Replacement activities is submitted in accordance with Code Case N-532-5. Similarly, in accordance with Revision 4. 1 ofthe IWE Program Plan, the OAR-i form for the Containment Inservice Inspection activities is submitted in accordance with Code Case N-532-5.

83 15 County Road 459 Steedman, MO 65077 AmerenMissouri.com

ULNRC-06630 March 18, 2021 Page 2 This letter does not contain new commitments.

Ifthere are any questions, please contact Mr. Tom Elwood at 314-225-1905.

JPKIm1p

Enclosure:

OAR-i forms (2)

Sincerely, Manager, Regulatory Affairs

ULNRC-06630 March 18, 2021 Page 3 cc:

Mr. Scott A. Morris Regional Administrator U. S. Nuclear Regulatory Commission Region IV 1600 East Lamar Boulevard Arlington, TX 76011-4511 Senior Resident Inspector Callaway Resident Office U.S. Nuclear Regulatory Commission

$201 NRC Road Steedman, MO 65077 Mr. M. Chawla Project Manager, Callaway Plant Office of Nuclear Reactor Regulation U.S. Nuclear Regulatory Commission Mail Stop O8B1A Washington, DC 20555-000 1

ULNRC-06630 March 18, 2021 Page 4 Index and send hardcopy to QA File A160.0761 Hardcopy:

Certrec Corporation 6500 West Freeway, Suite 400 FortWorth,TX 76116 (Certrec receives ALL attachments as long as they are non-safeguards and may be publicly disclosed.)

Electronic distribution for the following can be made via Other Situations ULNRC Distribution:

F. M. Diya B. L. Cox F. J. Bianco S. P. Banker R. C. Wink I. B. Elwood J. C. Claunch L. E. Eitel NSRB Secretary STARS Regulatory Affairs Mr. Jay Silberg (Pillsbury Winthrop Shaw Pittman LLP)

Ms. Kathleen McNelis (Public Service Commission)

Ms. Claire Eubanks (Public Service Commission)

El 70.0100 CALLAWAY NUCLEAR PLANT FORM OAR-I OWNERS ACTIVITY REPORT Report Number 24 Plant Callawav Enerav Center. 8315 County Road 459, Steedman. MO 65077 Unit No.

I Commercial service date 12119/1984 Refueling outage no.

24 (if applicable)

Current inspection interval 4Th fist, 2nd, 3rd, 4th, other)

Current inspection period 2

fist, 2nd, 3rd)

Edition and Addenda of Section Xl applicable to the inspection plans 2007 Edition with 2008 Addenda Date and revision of inspection plans 3/18/2019. Rev. 001 Edition and Addenda of Section Xl applicable to repair/replacement activities, if differentthan the inspection plans Same as insoectionolan.

Code Cases used for inspection and evaluation:

N-532-5. N-661-2 and N-716-f (if appticable, including cases modified by Case N-532 and later revisions)

CERTiFICATE OF CONFORMANCE I certify that (a) the statements made in this report are correct; (b) the examinations and tests meetthe Inspection Plan as required by the ASME Code, Section Xl; and (C) the repair/replacement activities and evaluations supporting the completion of 24 (refueling outage number) conform to t ir s of ection Xl.

Date 08-March-2021 CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and employed by of have inspected the items described in this Owners Activity Report, and state that, to the best of my knowledge and belief, the Owner has performed all activities represented by this report in accordance with the requirements of Section Xl.

By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the repair/replacement activities and evaluation described in this report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

N1 JL/

Endorsement)

(06/11)

CALLAWAY NUCLEAR PLANT TABLE I ITEMS WITH FLAWS OR RELEVANT CONDITIONS THAT REQUIRED EVALUATION FOR CONTINUED SERVICE Examination Category Item Descption Evaluation Descption and Item Number NONE

TABLE 2 ABSTRACT OF REPAIR/REPLACEMENT ACTIVITIES REQUIRED FOR CONTINUED SERVICE Code Class Item Description Description of Work Date Completed Repar/Replacement Plan Number NONE

E170.OJ 00 CALLAWAY NUCLEAR PLANT FORM OAR-I OWNERS ACTIVITY REPORT Report Number 24 Plant Callawav Energy Center, 8315 County Road 459. Steedman. MO 65077 Unit No.

I uac 12/19/1984 Refueling outage no.

24 (if applicable)

Current inspection interval 3rd (let, 2nd, 3rd, 4th, other)

Current inspection period J

(fat, 2nd, 3rd)

Edition and Addenda of Section Xl applicable to the inspection plans 2007 Edition with 2005 Addenda Date and revision of inspection plans WE Program: 10/1012079. Rev. 4.1 Edition and Addenda of Section Xl applicable to repair/replacement activities, if diffecentthan the inspection plans Same as insoection Dian.

Code Cases used for inspection and evaluation:

N-532-5 and N-765 Qf applicable, induthng casea modifled by Case N-532 and later revisiona)

CERTIFICATE OF CONFORMANCE I certify that (a) the statements made in this report are correct; (b) the examinations and tests meetthe Inspection Plan as required by the ASME Code,Section XI; and (c) the repair/replacement activities and evaluations supporting the completion of 24 (refueling outage number) conform to the requirements of Section XI.

Signed trfi*a?slI:3 Erjitir__

Date I 0-March-2021 Owner or Owners Designee Title

]

CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, h Idn a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and employed by of Cf have inspected the items described in this Owners Activity Report, and state that, to the best of my knowledge and belief, the Owner has performed all activities represented by this report in accordance with the requirements of Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the repair/replacement activities and evaluation described In this report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commission Pi413 i17 cjiJ 1 lnsp ota Si n

(National Board Number and Endorsement)

Date__________________

(06/11)

CALLAWAY NUCLEAR PLANT TABLE I ITEMS WITH FLAWS OR RELEVANT CONDITIONS THAT REQUIRED EVALUATION FOR CONTINUED SERVICE Examination Category Item Description Evaluation Description and Item Number E-A, E.1.I 1 Incore Sump Liner CR 202005276 While performing Job 17514095.500, IWE inspection ofthe lncore Pit, Degraded coatings were identified. After the first inspection on 10/7/20, QC notified R/C Helpers to perform additional cleaning of the pit and took the job to Stoppedw. QC reinspected on 10/8/20 after cleaning was performed and identified multiple areas of bubbled coatings. A paint scraper was used to expose the liner plate on all of these locations, so the WE exam could be completed. All areas identified had sound metal exposed and for the purpose of the IWE General Inspection, ESP ZZ-0I016 Section 3 and the Incore Pit, Area 31 was accepted. The Incore Pit will have coatings repaired in Refuel 25 to avoid degradation that would cause extensive structural repairs.

TABLE 2 ABSTRACT OF REPAIR/REPLACEMENT ACTIVITIES REQUIRED FOR CONTINUED SERVICE Code Class Item Description Descption of Work Date Completed Repair/Replacementi]