U-601238, Forwards Addl Info Re Relief Requests 5003 & 5004 Re Replacement Parts as Part of Inservice Insp Program
| ML20151P412 | |
| Person / Time | |
|---|---|
| Site: | Clinton |
| Issue date: | 08/03/1988 |
| From: | Holtzscher D ILLINOIS POWER CO. |
| To: | NRC OFFICE OF ADMINISTRATION & RESOURCES MANAGEMENT (ARM) |
| References | |
| U-601238, NUDOCS 8808100019 | |
| Download: ML20151P412 (3) | |
Text
?
U-601238 L30-88 ( 08- 03)-LP 1A.120
/LLINDIS PUWER COMPANY CLINToN POWER STATION. P.o. Box 678. CLINTON. ILLINCIS 61727 August 3, 1988 Docket No. 50-461 U. S. Nuclear Regulatory Commission Document Control Desk Washington, D.C.
20555
Subject:
Clinton Power Station Inservice Inspection
Dear Sir:
The letter from Janice A. Stevens to Frank A. Spangenberg dated July 19, 1988, requested additional information on relief requests 5003 and 5004. The requested information is attached.
If there are any questions, please contact me.
Sincerely yours, oh./
]
D. L. Holtzscher Acting Manager - Licensing and Safety DW/bj t Attachment cc: NRC Clinton Licensing Project Manager NRC Resident Inspector Regional Administrator, Region III, USNRC illinois Department of Nuclear Safety 1
4 i
s eso8100019 880803 k
I t
U-601238 L30-88 008 -03 )-LP 1A.120 Attachment Requested Information 1.
Clarify whether the replacement parts are identical to the original parts and were purchased from the original vendors.
If not, list all critical characteristics of these parts and verify that the replacement parts have the equivalent characteristics and level of quality as the original parts;
Response
The parts have not yet been procured. Each relief request identifies the original vendor as the vendor of the replacement parts. No relief is being requested from code design requirements.
Replacement parts will have the same functional characteristics as the original parts.
Requested Information 2.
Article IWA-7000 of the ASME Code,Section XI requires that replacement parts should meet the requirements of the edition of the Construction Code to which the original parts were constructed.
Identify the Code editions of the original parts and verify that the replacement parts meet all Code requirements except for ASHE certification; and
Response
This item has been addressed in Item 1 of the alternate testing section of the original relief requests.
In order to comply with this item, all parts shall meet the original construction code unless changes are reconciled with the design specification as described in IWA-7210.
The alternate testing proposed by Illinois Power (IP) ensures that code requirements except certification and stamping are met.
Requested Information 3.
As required by IWA-7000, if replacement parts are needed due to the failure of the original parta, an evaluation must be provided to ensure that the selected replacement parts are suitable.
Response
A replacement evaluation is performed for each replacement as required by IWA 7000.
Implementation of the replacement evaluation is described in the Clinton Power Station Inservice Inspection program manual.
No relief from the evaluation requirements is being requested.
1
j U-601238
'l
. L30-88(08 03 )-LP.
1A.120 Requested Information l
4.
Identify the vendors of.both the original and replacement parts'.
Response
As noted in Item 1 above, the original vendor will supply the j
replacement parts.
1 l
2
,