' filELECTRIC June 26,J987' c,,,,, o, c,,,,
Emytive Vice Ptreikat Uh S. Nuclear Regulatory Commission LATTN: -Document Control Desk o
Washington,lD.C.
20555 1
s
SUBJECT:
COMANCHE PEAK STEAM ELECTRIC STATION (CPSES) d DOCKET NOS. 50-445 AND 50-446
'ELECRICAL RACEWAY SUPPORT-SYSTEM
.SDAR:= CP-85-31 (INTERIM REPORT)'
. Gentlemen:
On December 5,1986 we notified you by our letter logged TXX-6138 of.a1 deficiency; involving the Unit 1 Class 1E Electrical-Raceway Support System l
which we deemed reportable under. the provisions, of 10CFR50.55(e). This is an-interim report submitted to status corrective' actions implemented to date..
Our latest report,. logged'TXX-6319 was submitted March 6,1987.
This deficiency involves the installation of Separation Barrier Material"(SBM)~
and' Radiant Energy Shield (RES) material on Unit 1 Class '1E Electrical Conduit.
Raceways without engineering. interdisciplinary, design review of. the proposed change. '-
. As a result 'of the completed evaluation:of conduit installations-affected by.
b the RES, twenty;(20) supports'will be modified and fifteen (15) new supports:
will be added. : Design change authorizations _ and travelers-have been approved 2
and-issued for-all modified and new supports.
Physical. work started in January 1987. and is currently 40% complete.
New and/or additional conduit installations requiring RES have been identified and are being evaluated in accordance with the revised interdiscipline l
procedural program'.
After completion of the program to ' determine the effects of the installation:
of RES on the Raceway' Support System, a similar program will be conducted to determine the effects of the installation of SBM.
'Our next report will be~ submitted by August 28, 1987.