= N=--

Log # TXX-6445 FE File # 10110 908.3

=

=

Ref # 10CFR50.55(e) 1UELECTRIC UUj$Na, May 15, 1987 U. S. Nuclear Regulate,ry Commission Attn: Document Control Desk Washington, D.C.

20555

SUBJECT:

COMANCHE PEAK STEAM ELECTRIC STATION (CPSES)

DOCKET NOS. 50-445 AND 50-446 WEATHER PROTECTION FOR CLASS IE COMP 0NENTS SDAR: CP-86-68 (INTERIM REPORT)

Gentlemen:

On October 2,1986, we verbally notified your.Mr. I. Barnes of a deficiency regarding provisions for weather protection of Class 1E components used in outdoor installations. This is an interim _ report of a potentially reportable item under the provisions of 10CFR50.55(e). Our most recent interim report was logged TXX-6226, dated January 21, 1987.

Our evaluation involving weather proofing of outdoor Class IE junction / terminal boxes is continuing. This program includes:

1.

Evaluation of engineering field inspections conducted in accordance with CPE-FVM-EE-054, "FVM to Acquire Data on Weatherproofing of all Outdoor Class IE Terminal / Junction Boxes and Associated Conduit Fittings," and a review of previous inspection documents to assess the adequacy of previous inspections, 2.

The initiation of NCRs and the analysis of discrepant installations, j

3.

Review of Specification 2323-ES-100, " Electrical Erection Specification", to assure adequate requirements for water-tight i

conduit connections for Class 1E outdoor pull / junction boxes, and 4.

Review of applicable quality control procedures.

l 8705220087 870515 l

PDR ADOCK 05000445

-[

S PDR 4

V r

i TXX-6445 May 15, 1987 Page 2 of 2 We will be unable to complete our assessment of this issue _ until the above activities are completed.

We anticipate submitting our next report by July 24, 1987.

Very truly yours, W. G. Counsil WJH/gj c - Mr. R. D. Martin - Region IV Mr.

D.' L. Kelley, RI - Region IV Mr. H. S. Phillips, RI - Region IV p r g-r w

y