MONTHYEARML20128C6671985-05-0909 May 1985
[table view]Application for Amend to License NPF-5,revising Tech Spec 3.8.2.6, Primary Containment Penetration Conductor Overcurrent Protective Devices to Remove All Setpoints or Modify Setpoints for Four Specific Breakers.Fee Paid ML20128C6851985-05-0909 May 1985 Proposed Changes to Tech Spec Table 3.8.2.6, Primary Containment Penetration Conductor Overcurrent Protective Devices, Removing All Setpoints or Modifying Setpoints for Four Specific Breakers ML20128B3891985-05-14014 May 1985 Amend 46 to License NPF-5,revising Overcurrent Trip Setpoints of Circuit Breakers for One Drywell Cooling Unit & Three Drywell Cooling Return Air Fans ML20128B3981985-05-14014 May 1985 Safety Evaluation Supporting Amend 46 to License NPF-5 05000366/LER-1985-017-01, :on 850430 & 0501,molded Case Circuit Breakers Trip Setpoints &/Or Breaker Locations Contrary to Specified Setpoints or Locations of Tech Spec Table 3.8.2.6-1.Caused by Inadequate Instructions.Tech Specs Amended1985-05-30030 May 1985
ML20133K3251985-07-22022 July 1985 Responds to NRC Re Violations Noted in Insp Repts 50-321/85-16 & 50-366/85-16.Corrective Actions:Proposed Tech Spec Change Re Testing Method for Molded Case Circuit Breakers Submitted on 850509 ML20134P9731985-08-30030 August 1985 Amended Application for Amend to License NPF-5,revising Tech Specs 3.8.2.6-1 to Delete All Info in Trip Setpoint & Response Time Columns & to Specify NEMA Std AB2-1980 as Testing Requirement for Molded Case Circuit Breakers IR 05000321/19850251985-08-30030 August 1985 Insp Rept 50-321/85-25 & 50-366/85-25 on 850806-09.No Violation or Deviation Noted.Major Areas Inspected:Emergency Preparedness Exercise ML20137E9381986-01-0909 January 1986 Safety Evaluation Supporting Amend 60 to License NPF-5 ML20137E9011986-01-0909 January 1986 Amend 60 to License NPF-5,revising Tech Specs to Delete Breaker Setpoints from Table 3.8.2.6-1 to Remove Ref to Setpoints from Surveillance Requirements & to Add Requirement That Breakers Be Tested Per NEMA AB-2-1980 1985-05-09 | |
Retrieved from "https://kanterella.com/w/index.php?title=TAC:57643&oldid=3376968"