MONTHYEARML20112J6311985-04-0101 April 1985
[table view]Proposed Changes to Tech Spec 3.7.10.1,treating Fire Suppression Pump C as Primary Pump & Disallowing Extended Inoperability ML20112J6211985-04-0101 April 1985 Application for Amends to Licenses NPF-9 & NPF-17,changing Tech Spec 3.7.10.1 to Treat Fire Suppression Pump C as Primary Pump & Disallow Extended Inoperability.Fee Paid ML20132C3991985-09-23023 September 1985 Responds to NRC 850910 Questions Re Fire Suppression Pump C. Repowering Existing Pump from Class 1E Diesel Would Cause Power to Be Unavailable During Loca.Total Blackout of Plant Switchyard Allowed W/O Effect on 44 Kv Feeder to Pump ML20138C8581985-10-14014 October 1985 Provides Info Re Fire Suppression Pumps.Any Pump Can Be Loaded on Diesel 1E.Pump a Powered from 6,900-volt Switchgear 2TB,Pump B Loaded from 6,900 Switchgear 1TD & Pump C Powered from 44-kV Substation.Diagrams Encl 1985-04-01 | |