- ML20202E598 (← links)
- ML20212H077 (← links)
- ML20212E981 (← links)
- ML20216B281 (← links)
- 05000446/LER-1997-004-01, :on 971108,gaps in Structural Components of Containment Sump Trash Racks Was Noted.Caused by Incomplete Corrective Actions Documents.Verified That Condition Does Not Negatively Interact W/Condition Reported in Unit 2 (← links)
- 05000445/LER-1998-005, :on 980617,functional Requirements of Hps Was Not IAW Design.Caused by Failure to Completely Evaluate FSAR Impact on Design Basis.Developed post-accident Recovery Guidance & Design Mod to Allow Use of 12 Inch Inlet Valve (← links)
- 05000445/LER-1993-001, :on 930118,trip Blocks Were Not in Place for Switch Manipulation & Reactor Trip Occurred While Restoring Ssps to Normal Lineup.Caused by Personnel Error.Event Reviewed & Training & Procedure Revised (← links)
- 05000445/LER-1992-027, :on 921220,actuation Relay Inadvertently Energized,Resulting in Premature Closure of Two Open Msivs. Caused by Personnel Error.Certification for Test Engineer Revoked & Training Conducted for Personnel (← links)
- 05000445/LER-1992-026, :on 921203,discovered That Monthly Surveillance to Check for & Remove Water in Train B DG Fuel Oil Storage Tank Not Performed During Allowable Time Period.Caused by Personnel Error.Surveillance Performed (← links)
- 05000445/LER-1993-005, :on 930401,discovered That Quarterly Valve Stroke Time Testing Not Performed for Safety Chilled Water Sys Prior to Violation Date of 930329 Due to Personnel Error.Subj Testing Performed (← links)
- 05000445/LER-1993-007, :on 930626,CR Alarm Received,Indicating Excessive Temp on Reactor Coolant Pump Motor Stator 1-04 & Manual Trip Initiated.Caused by RTD Failure.Rtd Terminations Disconnected & AOP Revised (← links)
- 05000446/LER-1993-004-01, :on 930514,failure to Satisfy TS Surveillance for Verification of Valve Position Due to Valve Discrepancies Discovered During DBD Review.Valve Cap & Clearance Installed (← links)
- 05000446/LER-1993-003-01, :on 930504,manual Reactor Trip Occurred Following Inadvertent Closure of Fwiv.Caused by Instrumentation Channel Error.Maint Performed on Affected Instrumentation Channels (← links)
- 05000445/LER-1993-006, :on 930426,failure to Satisfy TS Surveillance Requirement for Primary Plant ESF Exhaust Filtration Unit Noted.Caused by Poor Labeling,Specification of Wrong Procedure & Discrepancy in Parts List (← links)
- 05000445/LER-1993-004, :on 911116 & 920627,liquid Waste Processing Valve 1-7150 Exceeded Alert Criteria of 4 S.Caused by Failure to Adequately Review Test Results & Personnel Error. Personnel Indoctrinated & Test Controls Enhanced (← links)
- 05000446/LER-1993-002-01, :on 930315,personnel Error Leading to Failure to Satisfy TS SR for Feedwater Isolation Valve Temp Monitoring Identified.Procedures Revised to Clearly Address TS Requirements (← links)
- 05000445/LER-1993-003, :on 930226,spurious SIS Actuation from Train a Solid State Safeguards Sequencer Occurred.Caused by Failure of Instrument Used During Troubleshooting.Monitoring Device Removed & Sys Card Chassis Replaced (← links)
- 05000445/LER-1992-029, :on 921208,discovered Temporary Power Supply Lost to Panel 1PC1.Caused by Personnel Error.Engineering Will Hold Annual Training in self-verification for All Engineering Personnel (← links)
- 05000446/LER-1993-001-01, :on 930207,breaker Tripped at non-IE Instrument Power Distribution Panel to Allow Replacement of Breaker,Resulting in Containment Ventilation Isolation. Caused by Deenergized Relay.Drawing Revised (← links)
- 05000445/LER-1992-028, :on 921114 & 15,results of Pull Tests Indicated That 87 Clips in Train a & 40 Clips in Train B Experienced Failure.Caused by Mfg Installation Error.Procedures Revised & All Failed Connections Replaced (← links)
- 05000445/LER-1993-002, :on 930124,spurious Signal from Pressurizer Pressure Channel 2 Resulted in Overtemp Nitrogen 16 Reactor Trip.Caused by Instrument Failure During Surveillance Testing.Failed Component Replaced (← links)