- 05000302/LER-1980-030-03, /03L-0:on 800731,during Monthly Diesel Generator Surveillance,Emergency Diesel Generator B Tripped as Result of Separation of Turbocharger Discharge Ductwork Due to Sheared Bolts on Mounting Bracket.Caused by Vibration (← links)
- 05000302/LER-1980-038-03, /03L-0:on 800916,during ECCS Pump Operability test,DHV-111 B Decay Heat Pump Discharge Throttle Valve Would Not Control Flow in Automatic.Caused by Roller Nut Not Engaging Actuating Cam.Roller Nut Adjusted (← links)
- 05000302/LER-1980-039-03, /03L-0:on 800917,auxiliary Bldg Ventilation Exhaust Fan Failed.Caused by Failure of Two Blades in Fan Assembly.Fan Motor Was Repaired & New Fan Assembly Installed (← links)
- 05000302/LER-1980-033-03, /03L-0:on 800803,following Routine Sampling of Core Flood Tank A,Sample Isolation Valve CFV-11 Failed to Close.Caused by Failed Contact Rotor in Limitorque Operator. Contact Rotor 2 Replaced & Declared Operable (← links)
- 05000302/LER-1980-026-03, /03L-0:on 800714,while Performing SP-710 Rc Decay Heat Removal & Rc Makeup Sys Chemistry Surveillance Program, Chloride & Fluoride Concentrations Exceeded Limits.Caused by High Temp of Decay Heat Sys & Migration of Elements (← links)
- 05000302/LER-1980-027-01, /01T-0:on 800728,in Mode 5,while Performing OP-401 Core Flooding Sys,Check Valve CFV-79 Failed Allowing About 500 Gallons of Liquid to Enter Nitrogen Sys Via NGV-4. Apparently Caused by CFV-79 Failure & Open NGV-4 (← links)