- 05000397/LER-1983-009-03, /03L:on 831222,fire Damper WOA-SMD-1A Manually Propped Open.Caused by Link Holding Damper Open Fusing Due to Influx of Dust to Activating Detector.New Link Installed (← links)
- 05000397/LER-1983-008-03, /03L:on 831222,damper WOA-SMD-1B Malfunctioned. Guillotine Damper Binded in Track & Was Left in Open Position.Cause Unknown (← links)
- 05000397/LER-1983-007-03, /03L:on 831222,fire Hydrant FP-HT-1G Did Not Drain & Froze During Cold Weather.Caused by Contractor Inadvertently Blocking Drain Port for Hydrant While Pouring Concrete.Hydrant Repaired (← links)
- 05000397/LER-1983-006-03, /03L:on 831222,fire-rated Door D-104 Violated, Causing Loss of Fire Boundary Integrity.Caused by fire-rated Door Closing,Pinching Welding Lead & Melting Hole in Door. Door Replaced (← links)
- 05000397/LER-1983-005-03, /03L:on 831223,fire-rated Seals Removed to Perform Const Work,Causing Loss of Fire Boundary Integrity,Per Tech Specs.Caused by Plant Mod.Seals Will Be Replaced After Const Work Completed (← links)
- 05000397/LER-1983-004-03, /03L:on 831222,loss of Fire Detection Instrumentation Occurred at 606-ft Elevation of Reactor Bldg.Caused by Condensation Shorting Out Detection Sys.Power Supply Replaced & Condensation Source Being Corrected (← links)
- 05000397/LER-1983-003-03, /03L:on 831222,walk Down Revealed That Fire Dampers WMA-FD-1,2,7,8,9,10,11,14,15,18 & DRA-FD-34-1 Did Not Comply W/Ul Fire Rating.Caused by Vendor Cutting Dampers to Required Size (← links)
- 05000397/LER-1983-002-03, /03L-0:on 831231,discovered Fire Protection Storage Water Level in FP-TK-100 Less than 280,000 Gallons. Caused by Air Binding of Filter Effluent Pump While FP-P-107 in Manual Mode Due to Inadequate Procedural Instructions (← links)