- ML20009F906 (← links)
- 05000348/LER-1981-043-03, /03L-0:on 810602,sequencer Associated W/Diesel Generator Failed to Meet Time Requirement for Picking Up Step 2.Caused by Setpoint Drift.Agastat Timer Adjusted & Sequencer Returned to Svc (← links)
- 05000348/LER-1981-042-03, /03L-0:on 810610,pump Supplying Containment Atmosphere Particulate & Gaseous Radioactivity Monitoring Sys Failed to Start.Caused by Filter Paper Not Advancing Due to Paper Drive Malfunction.Drive Mechanism Adjusted (← links)
- 05000348/LER-1981-041-03, /03L-0:on 810606,diesel Generator Found Incapable of Automatically Starting Due to locked-in Low Lube Oil Pressure Alarm.Caused by Inadequate Procedural Guidance. Procedures Revised (← links)