- ML19345B806 (← links)
- 05000348/LER-1980-072-03, /03L-0:on 801031,river Water Train B Declared Inoperable When Pump 5 Tripped & Would Not Restart.Caused by Breaker Hea 86 Lockout Relay & 50G Instantaneous Overcurrent Relay Actuation (← links)
- 05000348/LER-1980-071-03, /03L-0:on 801027 & 28,containment Atmosphere Particuulate & Gaseous Radioactivity Monitoring Sys (R11 & R12) Declared Inoperable Due to Low Flow Pump Trips.Caused by Failing Bearings & Partially Opened Isolation Valve (← links)
- 05000348/LER-1980-070-03, /03L-0:on 801028,svc Water Bldg Train a Battery Sys Declared Inoperable Due to Low Cell Specific Gravity. Caused by Close Terminal Proximity & Poor Post Seal Design Allowing Formation of Acid Residue Which Shunted Current (← links)
- 05000348/LER-1980-068-03, /03L-0:on 801031,B Train River Water Pumps Declared Inoperable Due to Inadequate Lube & Cooling Water Flow.Caused by Dirty Strainers.Strainers Blown Down & Cleaned (← links)
- 05000348/LER-1980-066-03, /03L-0:on 801026,containment Atmosphere Particulate & Gaseous Radioactivity Monitoring Sys (R11 & R12) Declared Inoperable.Caused by Clogged Filter Paper from Stuck Filter Paper Takeup Reel Causing Pump Low Flow Trips (← links)
- 05000348/LER-1980-069-01, /01T-0:on 801112,water for Lubrication & Cooling of a Train Svc Water Pumps Found to Be Provided by B Train Water Header & Vice Versa.Caused by Design Error.Design Change to Provide Correct Separation Completed (← links)