- ML19289G223 (← links)
- 05000368/LER-1979-057-04, /04L-0 on 790718:radwaste Area Exhaust Radiation Monitor Found Inoperable.Caused by Broken Coupling on Radiation Monitor Sample Pump.Pump Coupling Replaced & Monitor Returned to Svc (← links)
- 05000368/LER-1979-056-03, /03L-0 on 790713:station Batteries Surveillance Insp Not Performed on Schedule.Caused by Personnel Oversight.Importance of Program Discussed W/Supervisor (← links)
- 05000368/LER-1979-054-03, /03L-0 on 790716:main Feedwater Valve a Failed Shut.Caused by Frozen Inboard Bearing on Valve Operator Motor.Bearing Replaced,Motor Reinstalled & Valve stroke-tested Satisfactorily.Valve Declared Operable (← links)
- 05000368/LER-1979-053-03, /03L-0 on 790713:control Room Air Conditioner Compressor Failed to Start from Control Room Panel.Caused by Casting Plug Lodged in Compressor Valve.Plug Removed,Unit Recharged & Declared Operable (← links)