- 05000334/LER-1980-041-03, /03L-0:on 800502,during Test,Supplementary Leak Collection & Exhaust Fan Tripped.Apparently Caused by Loose Lead.Motor Lead Reconditioned + (01:25:21, 2 January 2025)
- 05000368/LER-1980-032-03, /03L-0:on 800525,during Mode 1 Operation,Plant Computer Failed on Three Occasions.Cause Undetermined. Computer Software Diagnostic Routines or Backup Computer Sys Will Be Purchased to Alleviate Problems + (01:25:23, 2 January 2025)
- 05000327/LER-1980-081, Forwards LER 80-081/03L-0 + (01:25:25, 2 January 2025)
- 05000327/LER-1980-078-03, /03L-0:on 800526,during Mode 4 Operation,Boron Concentration in RWST Measured 2124 Ppm.Caused by Boron Concentration Makeup Being Too High.Boron Diluted to Proper Concentration + (01:25:26, 2 January 2025)
- 05000263/LER-1980-022, Forwards LER 80-022/03L-0 + (01:25:28, 2 January 2025)
- 05000306/LER-1980-016-03, /03L-0:on 800529,during Instrument Calibr, Instrument Was Dropped on Trip Throttle Valve Linkage, Tripping Valve & Making Pump Inoperable for 3 Minutes. Caused by Personnel Error + (01:25:30, 2 January 2025)
- 05000327/LER-1980-082, Forwards LER 80-082/03L-0 + (01:25:31, 2 January 2025)
- 05000368/LER-1980-032, Forwards LER 80-032/03L-0 + (01:25:33, 2 January 2025)
- 05000334/LER-1980-041, Forwards LER 80-041/03L-0 + (01:25:36, 2 January 2025)
- 05000327/LER-1980-078, Forwards LER 80-078/03L-0 + (01:25:37, 2 January 2025)
- 05000306/LER-1980-016, Forwards LER 80-016/03L-0 + (01:25:39, 2 January 2025)
- 05000327/LER-1980-080-03, /03L-0:on 800527,during Test on B Train of Auxiliary Bldg Gas Treatment Sys,Control Fuse Failed & Tripped Fan Motor Supply Breaker.Cause Unknown.Fuse Replaced & Sys Declared Operable + (01:25:41, 2 January 2025)
- 05000325/LER-1980-033-03, /03L-0:on 800526,while Performing Penetrant Test 1.10,count Rate for Source Range Monitors B & C Did Not Decrease When Detectors Were Removed from Core.Caused by Blown Fuses & Height Discriminator Maladjustment + (01:25:42, 2 January 2025)
- 05000333/LER-1980-053-03, /03L-0:on 800529,during Normal Refueling,Review Revealed That Temporary Changes to Instrument Maint Procedure Made on 800417 Had Not Been Reviewed by Porc. Caused by Administrative Error.Porc Reviewed Changes + (01:25:44, 2 January 2025)
- 05000366/LER-1980-068-03, While Performing Primary Containment Recombiner Sys Functional Test,Recombiner Sheath Temp Failed to Remain within Tech Spec.Caused by Setpoint Being Set Too High + (01:25:46, 2 January 2025)
- ML19318C479 + (01:25:48, 2 January 2025)
- 05000327/LER-1980-083-03, /03L-0:on 800529,pump Motor on O-RM-90-134 Burned Out Causing Common Circuit Breaker on O-RM-90-134/141 & 1-RM-90-112 to Trip.Cause Unknown.Motor Replaced + (01:25:49, 2 January 2025)
- 05000325/LER-1980-033, Forwards LER 80-033/03L-0 + (01:25:51, 2 January 2025)
- 05000327/LER-1980-080, Forwards LER 80-080/03L-0 + (01:25:53, 2 January 2025)
- 05000333/LER-1980-053, Forwards LER 80-053/03L-0 + (01:25:54, 2 January 2025)
- 05000366/LER-1980-068, Forwards Revised LER 80-068/03X-1 + (01:25:56, 2 January 2025)
- 05000325/LER-1980-032-03, /03L-0:on 800525,when Rod Was Selected,Rod Block Monitor B Inoperable Light on Rod Block Monitor Panel Illuminated.Cause Unknown.Problem Could Not Be Reproduced or Identified When Troubleshooting Sys + (01:25:59, 2 January 2025)
- ML19318C468 + (01:26:01, 2 January 2025)
- 05000366/LER-1980-089-03, /03L-0:on 800530,while Performing HNP-2-3315,torus Suction Valves 2E41-F041 & 2E41-F042 Failed When Given Open Signal.Torus Valves Shorted Out Due to Condensation in HPCI Room.Cause of Condensation Was Steam Leakage Around S + (01:26:06, 2 January 2025)
- 05000327/LER-1980-053-03, /03L-0:on 800526,svc Bldg Vent Monitor O-RM-90-132B Declared Inoperable Due to Loss of Flow.Caused by Inoperative Radiation Monitor Sample Vacuum Pump.Other Monitor Sample Pump Valved in & Monitor Returned to Svc + (01:26:08, 2 January 2025)
- 05000325/LER-1980-032, Forwards LER 80-032/03L-0 + (01:26:09, 2 January 2025)
- 05000295/LER-1980-029-03, /03L-0:on 800531,while Removing Insulation to Repair Leak on Discharge Line to Boric Acid Filter 1,heat Trace on Circuits Ome 190/205 Were Damaged.Caused by Numerous Nicks in Heat Trace by Personnel Effecting Repair + (01:26:11, 2 January 2025)
- 05000327/LER-1980-053, Forwards LER 80-053/03L-0 + (01:26:14, 2 January 2025)
- ML19318C459 + (01:26:15, 2 January 2025)
- 05000333/LER-1980-052-03, /03L-0:on 800528,during Refueling Operations, Refuel Bridge Movement to Over Core Area Did Not Generate Control Rod Withdrawal Block Per Tech Specs.Caused by Drift at Bridge Position Sensing Limit Switch.Switch Adjusted + (01:26:18, 2 January 2025)
- 05000366/LER-1980-089, Forwards LER 80-089/03L-0 + (01:26:20, 2 January 2025)
- 05000295/LER-1980-029, Forwards LER 80-029/03L-0 + (01:26:28, 2 January 2025)
- 05000327/LER-1980-083, Forwards LER 80-083/03L-0 + (01:26:31, 2 January 2025)
- ML19318C449 + (01:26:32, 2 January 2025)
- 05000295/LER-1980-028-03, /03L-0:on 800524,while Performing Diesel Generator Loading Test on 1B Diesel Generator,Engine Tripped After Running 5 Minutes at Full Load.Caused by Air Leak on Supply Line Fitting to Fuel Shutoff Pistons.Fitting Replaced + (01:26:34, 2 January 2025)
- 05000333/LER-1980-052, Forwards LER 80-052/03L-0 + (01:26:35, 2 January 2025)
- 05000333/LER-1980-054-04, /04L-0:on 800530,during Normal Shutdown,Both Recorders for Gaseous Release Rate from Reactor Bldg Ventilation Sys & Plant Process Computer Were Out of Order During Same 16-h Period.Caused by Personnel Error + (01:26:37, 2 January 2025)
- 05000295/LER-1980-028, Forwards LER 80-028/03L-0 + (01:26:39, 2 January 2025)
- 05000333/LER-1980-054, Forwards LER 80-054/04L-0 + (01:26:41, 2 January 2025)
- ML19318C440 + (01:26:42, 2 January 2025)
- ML19318C439 + (01:26:42, 2 January 2025)
- ML19318C437 + (01:26:43, 2 January 2025)
- ML19318C438 + (01:26:43, 2 January 2025)
- ML19318C435 + (01:26:44, 2 January 2025)
- ML19318C433 + (01:26:44, 2 January 2025)
- ML19318C432 + (01:26:45, 2 January 2025)
- ML19318C431 + (01:26:46, 2 January 2025)
- ML19318C430 + (01:26:47, 2 January 2025)
- ML19318C429 + (01:26:48, 2 January 2025)
- ML19318C427 + (01:26:49, 2 January 2025)
- ML19318C426 + (01:26:50, 2 January 2025)