Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- ML19257C579 + (ML19257C579)
- ML19257C580 + (ML19257C580)
- ML19257C581 + (ML19257C581)
- ML19257C582 + (ML19257C582)
- ML19257C583 + (ML19257C583)
- 05000298/LER-1979-038, Forwards LER 79-038/03L-0 + (ML19257C584)
- ML19257C585 + (ML19257C585)
- ML19257C586 + (ML19257C586)
- 05000272/LER-1979-074, Forwards LER 79-074/03L-0 + (ML19257C587)
- ML19257C588 + (ML19257C588)
- 05000298/LER-1979-038-03, /03L-0:on 791130,during Normal Operation, Suppression Chamber Level Instrument PC-LI-12 Failed Downscale.Caused by Failure of Power Supply.Power Supply Replaced & Proper Indication Verified + (ML19257C589)
- ML19257C590 + (ML19257C590)
- ML19257C591 + (ML19257C591)
- ML19257C592 + (ML19257C592)
- 05000298/LER-1979-039, Forwards LER 79-039/03L-0 + (ML19257C593)
- ML19257C594 + (ML19257C594)
- 05000272/LER-1979-074-03, /03L-0:on 791225,during Startup Operations,Routine Shift Operability Test Showed Auxiliary Alarm Typewriter Was Not Operating Properly.Caused by Failed Components in Typewriter Logic Control.Logic Control Boards Replaced + (ML19257C595)
- ML19257C596 + (ML19257C596)
- ML19257C597 + (ML19257C597)
- 05000333/LER-1979-115, Forwards LER 79-115/03X-1 + (ML19257C598)
- ML19257C599 + (ML19257C599)
- 05000295/LER-1979-093, Forwards LER 79-093/03L-0 + (ML19257C600)
- 05000333/LER-1979-115-03, /03X-1:on 791221,during Normal Operation,Personnel Noted Low Flow Alarms Associated W/Stack Gas Radiation Monitor Sys.Caused by Plugged Sample Line Common to Both Sample Pumps & Monitors.Sample Line Cleared W/Nitrogen + (ML19257C602)
- 05000295/LER-1979-093-03, /03L-0:on 791225,radioactivity Analysis of Fire Sump Discharge Sample Was Overlooked While Units Were in Cold Shutdown.Caused by Personnel Error.Computerized Sys to Provide Daily Monitoring Will Be Implemented + (ML19257C603)
- 05000219/LER-1979-043, Forwards LER 79-043/036-0 + (ML19257C604)
- ML19257C605 + (ML19257C605)
- ML19257C606 + (ML19257C606)
- 05000298/LER-1979-042, Forwards LER 79-042/03L-0 + (ML19257C607)
- ML19257C608 + (ML19257C608)
- 05000265/LER-1979-030, Forwards LER 79-030/03L-0 + (ML19257C609)
- ML19257C610 + (ML19257C610)
- ML19257C611 + (ML19257C611)
- ML19257C612 + (ML19257C612)
- ML19257C613 + (ML19257C613)
- ML19257C614 + (ML19257C614)
- 05000298/LER-1979-042-03, /03L-0:on 791223,during Routine Check,Rhr Pump 1D Breaker Found Not Charged.Rhr Pump 1D Could Not Operate. Caused by Loose Screw Holding Wire on Latch Monitoring Switch Preventing Charging Motor Operation.Tightened Screw + (ML19257C615)
- 05000219/LER-1979-043-03, /03L-0:on 791228,while Performing Surveillance Test on Reactor Bldg to Suppression Chamber Air Operated Vacuum Breakers,Valve V-26-16 Failed.Cause Undetermined. Valve to Be Inspected During Outage & Tested After Maint + (ML19257C616)
- 05000265/LER-1979-030-03, /03L-0:on 791228,while Performing Surveillance Procedure Qos 30-2,bed Plate Drain Valve AO 2-4999-59 Failed to Close When Float Switch Was Activated.Caused by Component Failure.Corrective Maint Underway + (ML19257C617)
- 05000336/LER-1979-041, Forwards LER 79-041/03L-0 + (ML19257C618)
- ML19257C619 + (ML19257C619)
- ML19257C620 + (ML19257C620)
- 05000298/LER-1979-039-03, /03L-0:on 791129,suppression Chamber Inboard Vent Isolation Valve PC-230MV Not Operable W/Control Switch & No Position Indication Observed in Control Room.Caused by Random Failure.Rotor Replaced W/Qualified Part + (ML19257C621)
- ML19257C622 + (ML19257C622)
- 05000336/LER-1979-041-03, /03L-0:on 791228,while Performing Surveillance, HPSI Injection Valves 2-SI-616 & 626 Overtravelled 3%.Insp of Valves Showed No Apparent Damage.Attempt to Repeat Overtravel Was Unsuccessful + (ML19257C624)
- ML19257C625 + (ML19257C625)
- ML19257C626 + (ML19257C626)
- 05000254/LER-1979-034, Forwards Updated LER 79-034/03L-1 + (ML19257C627)
- ML19257C628 + (ML19257C628)
- ML19257C629 + (ML19257C629)
- ML19257C631 + (ML19257C631)
- 05000302/LER-1979-112, Supplemental Info to LER 79-112/04X-0:on 800109,marine Plant & Vegetation Samples Had LLD Greater than Ets.Caused by Inadequate Sample Time & Use of Different Analyzing Equipment.No Corrective Action Proposed + (ML19257C632)