Browse wiki

Jump to navigation Jump to search
At 2125 on 4/24/15, 1R-2, Containment VessAt 2125 on 4/24/15, 1R-2, Containment Vessel Area Radiation Detector failed. Previously, 1R-7, Incore Seal Table Area Radiation Detector, had failed on 4/20/15. The compensatory measure for 1R-2 out-of-service is to verify 1R-7 operating properly and the compensatory measure for 1R-7 out-of-service is to verify 1R-2 operating properly. With both monitors out-of-service and Unit 1 operating in Mode 5, no compensatory measure is available that will allow timely classification of two Emergency Action Levels (EALs) - Notification of Unusual Event (NUE) classification (RU2.2) and Alert classification (RA3.2). This results in a Loss of Emergency Assessment Capability while 1R-2 and 1R-7 are concurrently out-of-service. This is a reportable condition per 10 CFR 50.72(b)(3)(xiii).</br>Monitoring of radiological conditions in Unit 1 Containment showed no indication of RCS leakage or elevated radiation levels prior to the failure of 1R-2. Unit 1 Containment also remains monitored by 1R-48, Containment Hi Range Area Radiation Detector A and 1R-49, Containment Hi Range Area Radiation Detector B, which currently indicate normal radiation levels. Unit 1 Shield Building Stack is also monitored by 1R-50, Shield Building High Range Vent Gas Radiation Detector, which also currently indicates normal radiation levels. Additionally, a temporary portable radiation monitor has been placed near the location of 1R-2 and is being continuously monitored.</br>The plant remains in a safe condition and there was no effect to the health and safety of the public.</br>The licensee has notified the NRC Resident Inspector.e has notified the NRC Resident Inspector.  +
02:25:00, 25 April 2015  +
51,013  +
04:10:00, 25 April 2015  +
02:25:00, 25 April 2015  +
At 2125 on 4/24/15, 1R-2, Containment VessAt 2125 on 4/24/15, 1R-2, Containment Vessel Area Radiation Detector failed. Previously, 1R-7, Incore Seal Table Area Radiation Detector, had failed on 4/20/15. The compensatory measure for 1R-2 out-of-service is to verify 1R-7 operating properly and the compensatory measure for 1R-7 out-of-service is to verify 1R-2 operating properly. With both monitors out-of-service and Unit 1 operating in Mode 5, no compensatory measure is available that will allow timely classification of two Emergency Action Levels (EALs) - Notification of Unusual Event (NUE) classification (RU2.2) and Alert classification (RA3.2). This results in a Loss of Emergency Assessment Capability while 1R-2 and 1R-7 are concurrently out-of-service. This is a reportable condition per 10 CFR 50.72(b)(3)(xiii).</br>Monitoring of radiological conditions in Unit 1 Containment showed no indication of RCS leakage or elevated radiation levels prior to the failure of 1R-2. Unit 1 Containment also remains monitored by 1R-48, Containment Hi Range Area Radiation Detector A and 1R-49, Containment Hi Range Area Radiation Detector B, which currently indicate normal radiation levels. Unit 1 Shield Building Stack is also monitored by 1R-50, Shield Building High Range Vent Gas Radiation Detector, which also currently indicates normal radiation levels. Additionally, a temporary portable radiation monitor has been placed near the location of 1R-2 and is being continuously monitored.</br>The plant remains in a safe condition and there was no effect to the health and safety of the public.</br>The licensee has notified the NRC Resident Inspector.e has notified the NRC Resident Inspector.  +
Has query"Has query" is a predefined property that represents meta information (in form of a <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Subobject">subobject</a>) about individual queries and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
00:00:00, 25 April 2015  +
Modification date"Modification date" is a predefined property that corresponds to the date of the last modification of a subject and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
01:47:55, 2 March 2018  +
04:10:00, 25 April 2015  +
false  +
false  +
0.0729 d (1.75 hours, 0.0104 weeks, 0.0024 months)  +
1R-50 +, 1R-2 +, 1R-7 +, 1R-48 +  and 1R-49 +
02:25:00, 25 April 2015  +
Loss of Emergency Assessment Capability Due to Out-Of-Service Radiation Monitors  +
URL"URL" is a <a href="/Special:Types/URL" title="Special:Types/URL">type</a> and predefined property provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a> to represent URI/URL values.