Browse wiki

Jump to navigation Jump to search
100  +  and 87  +
At 1550 (CDT) on September 19, 2016, DresdAt 1550 (CDT) on September 19, 2016, Dresden received the Methyl Iodide Penetration test results for the Control Room Emergency Ventilation (CREVS) charcoal. The test results did not meet technical specification acceptance criteria. This results in the inoperability of CREVS. CREVS is a single train system and therefore is reportable per 10CFR50.72(b)(3)(v)(D). The Air Filtration Unit (AFU) is required to operate during a design basis accident to maintain Main Control Room habitability. This places unit 2 and unit 3 in a 7 day LCORA (Limiting Condition of Operation Required Action) per Tech Spec 3.7.4 Required Action A.1.</br>The licensee notified the NRC Resident Inspector.</br>* * * UPDATE AT 1635 EDT ON 03/23/17 FROM HENRY WATERS TO S. SANDIN * * *</br>The licensee is retracting this report based on the following:</br>The purpose of this notification is to retract ENS notification 52253 made on September 19th, 2016, for Dresden Nuclear Power Station. After further evaluation and testing, it has been determined that the Control Room Emergency Ventilation System (CREVS) charcoal would have fulfilled its safety function given the Methyl Iodide Penetration test results. The initial tests were performed with a 2 inch bed depth due to a difference in batches used in each charcoal filter, but testing at a 4 inch bed depth is the correct testing methodology for Dresden's configuration. At a 4 inch bed depth, the test results met the Technical Specification acceptance criteria with significant margin. Therefore, this event does not meet the criteria of 10 CFR 50.72(b)(3)(v)(D) and the ENS report is being retracted.</br>The NRC Resident Inspector has been notified.</br>Notified R3DO (Orlikowski).been notified. Notified R3DO (Orlikowski).  +
20:50:00, 19 September 2016  +
52,253  +
21:40:00, 19 September 2016  +
20:50:00, 19 September 2016  +
At 1550 (CDT) on September 19, 2016, DresdAt 1550 (CDT) on September 19, 2016, Dresden received the Methyl Iodide Penetration test results for the Control Room Emergency Ventilation (CREVS) charcoal. The test results did not meet technical specification acceptance criteria. This results in the inoperability of CREVS. CREVS is a single train system and therefore is reportable per 10CFR50.72(b)(3)(v)(D). The Air Filtration Unit (AFU) is required to operate during a design basis accident to maintain Main Control Room habitability. This places unit 2 and unit 3 in a 7 day LCORA (Limiting Condition of Operation Required Action) per Tech Spec 3.7.4 Required Action A.1.</br>The licensee notified the NRC Resident Inspector.</br>* * * UPDATE AT 1635 EDT ON 03/23/17 FROM HENRY WATERS TO S. SANDIN * * *</br>The licensee is retracting this report based on the following:</br>The purpose of this notification is to retract ENS notification 52253 made on September 19th, 2016, for Dresden Nuclear Power Station. After further evaluation and testing, it has been determined that the Control Room Emergency Ventilation System (CREVS) charcoal would have fulfilled its safety function given the Methyl Iodide Penetration test results. The initial tests were performed with a 2 inch bed depth due to a difference in batches used in each charcoal filter, but testing at a 4 inch bed depth is the correct testing methodology for Dresden's configuration. At a 4 inch bed depth, the test results met the Technical Specification acceptance criteria with significant margin. Therefore, this event does not meet the criteria of 10 CFR 50.72(b)(3)(v)(D) and the ENS report is being retracted.</br>The NRC Resident Inspector has been notified.</br>Notified R3DO (Orlikowski).been notified. Notified R3DO (Orlikowski).  +
Has query"Has query" is a predefined property that represents meta information (in form of a <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Subobject">subobject</a>) about individual queries and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
100  +  and 87  +
00:00:00, 23 March 2017  +
Modification date"Modification date" is a predefined property that corresponds to the date of the last modification of a subject and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
08:11:32, 16 November 2024  +
21:40:00, 19 September 2016  +
false  +
0.0346 d (0.83 hours, 0.00494 weeks, 0.00114 months)  +
20:50:00, 19 September 2016  +
Control Room Emergency Ventilation Charcoal Not Meeting Acceptance Criteria  +
URL"URL" is a <a href="/Special:Types/URL" title="Special:Types/URL">type</a> and predefined property provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a> to represent URI/URL values.
2  +  and 3  +