Browse wiki

Jump to navigation Jump to search
100  +
At (2258) CST, on January 5, 2016, with thAt (2258) CST, on January 5, 2016, with the plant operating at 100 percent power, the main control room alarm indicating high pressure in the auxiliary building actuated. Operators confirmed that the building pressure, corrected for temperature, indicated slightly positive, whereas the building pressure limit in Technical Specifications is 0.0 - 3.0 inches of water negative pressure. Secondary containment was declared inoperable, and the Division 2 standby gas system was started. This action restored building pressure to the acceptable range, and the building was declared operable at (0027 CST) on January 6.</br>This condition is being reported in accordance with 10 CFR 50.72(b)(3)(v)(C) as an event that caused the secondary containment to be potentially incapable of performing its safety function. The NRC Senior Resident Inspector was notified.RC Senior Resident Inspector was notified.  +
04:58:00, 6 January 2016  +
51,637  +
09:38:00, 6 January 2016  +
04:58:00, 6 January 2016  +
At (2258) CST, on January 5, 2016, with thAt (2258) CST, on January 5, 2016, with the plant operating at 100 percent power, the main control room alarm indicating high pressure in the auxiliary building actuated. Operators confirmed that the building pressure, corrected for temperature, indicated slightly positive, whereas the building pressure limit in Technical Specifications is 0.0 - 3.0 inches of water negative pressure. Secondary containment was declared inoperable, and the Division 2 standby gas system was started. This action restored building pressure to the acceptable range, and the building was declared operable at (0027 CST) on January 6.</br>This condition is being reported in accordance with 10 CFR 50.72(b)(3)(v)(C) as an event that caused the secondary containment to be potentially incapable of performing its safety function. The NRC Senior Resident Inspector was notified.RC Senior Resident Inspector was notified.  +
Has query"Has query" is a predefined property that represents meta information (in form of a <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Subobject">subobject</a>) about individual queries and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
100  +
00:00:00, 6 January 2016  +
Modification date"Modification date" is a predefined property that corresponds to the date of the last modification of a subject and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
22:16:58, 24 September 2017  +
09:38:00, 6 January 2016  +
false  +
0.195 d (4.67 hours, 0.0278 weeks, 0.0064 months)  +
04:58:00, 6 January 2016  +
Secondary Containment Declared Inoperable  +
URL"URL" is a <a href="/Special:Types/URL" title="Special:Types/URL">type</a> and predefined property provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a> to represent URI/URL values.
1  +