A fire penetration on the Unit 1 reactor bA fire penetration on the Unit 1 reactor building 158 foot elevation was discovered to be degraded such that the associated wall would not meet Appendix R requirements as a 3-hour barrier. In the event of a postulated fire in either of the affected fire areas, separated by the affected penetration, both Unit 1 safe shutdown paths could be compromised. Given this information, the determination was made that this condition meets the reporting criteria of 10CFR50.72(b)(3)(ii)(B).</br>Compensatory measures were established in accordance with the plant's Fire Hazard Analysis (FHA). The presence of the compensatory measures in addition to automatic fire detection in these fire areas ensure that the safe shutdown paths are preserved until the degraded condition can be corrected.</br>Condition Report: 865615</br>The NRC Resident Inspector has been informed. NRC Resident Inspector has been informed.  +
07:07:00, 13 September 2014  +
09:53:00, 13 September 2014  +
07:07:00, 13 September 2014  +
A fire penetration on the Unit 1 reactor bA fire penetration on the Unit 1 reactor building 158 foot elevation was discovered to be degraded such that the associated wall would not meet Appendix R requirements as a 3-hour barrier. In the event of a postulated fire in either of the affected fire areas, separated by the affected penetration, both Unit 1 safe shutdown paths could be compromised. Given this information, the determination was made that this condition meets the reporting criteria of 10CFR50.72(b)(3)(ii)(B).</br>Compensatory measures were established in accordance with the plant's Fire Hazard Analysis (FHA). The presence of the compensatory measures in addition to automatic fire detection in these fire areas ensure that the safe shutdown paths are preserved until the degraded condition can be corrected.</br>Condition Report: 865615</br>The NRC Resident Inspector has been informed. NRC Resident Inspector has been informed.  +
Has query"Has query" is a predefined property that represents meta information (in form of a <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Subobject">subobject</a>) about individual queries and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
00:00:00, 13 September 2014  +
Modification date"Modification date" is a predefined property that corresponds to the date of the last modification of a subject and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
22:19:16, 24 September 2017  +
09:53:00, 13 September 2014  +
false  +
0.115 d (2.77 hours, 0.0165 weeks, 0.00379 months)  +
07:07:00, 13 September 2014  +
Fire Penetration Did Not Meet Appendix R Requirements  +