This report describes an invalid actuationThis report describes an invalid actuation of the Unit 2, Train A (2-01) Emergency Diesel Generator (EDG) that occurred on April 22, 2014. This report is being made in accordance with 10CFR50.73(a)(2)(iv)(A). 10CFR50.73(a)(1) states, in part, 'In the case of an invalid actuation reported under 10CFR50.73(a)(2)(iv), other than actuation of the Reactor Protection System (RPS) when the reactor is critical, the licensee may, at its option, provide a telephone notification to the NRC Operations Center within 60 days after discovery of the event instead of submitting a written LER.'</br>On April 22, 2014, Comanche Peak Nuclear Power Plant Unit 2 was in Mode 5 during the 14th refueling outage. At approximately 0830 CDT, while performing a lockout test on EDG 2-01, the Reactor Operator made a place keeping error that resulted in EDG 2-01 starting and rolling up to approximately 300 RPM. The start signal should have been blocked as part of the test. However, a step was skipped due to a place keeping error and this resulted in an inadvertent start of EDG 2-01 during the performance of a subsequent step.</br>The specific train and system that actuated was the Unit 2, Train A, Emergency Diesel Generator. During the inadvertent EDG start the system started and functioned correctly, and the EDG only reached 300 RPM before it was shut down.</br>The licensee has notified the NRC Resident Inspector.e has notified the NRC Resident Inspector.  +
13:30:00, 22 April 2014  +
15:19:00, 19 June 2014  +
13:30:00, 22 April 2014  +
This report describes an invalid actuationThis report describes an invalid actuation of the Unit 2, Train A (2-01) Emergency Diesel Generator (EDG) that occurred on April 22, 2014. This report is being made in accordance with 10CFR50.73(a)(2)(iv)(A). 10CFR50.73(a)(1) states, in part, 'In the case of an invalid actuation reported under 10CFR50.73(a)(2)(iv), other than actuation of the Reactor Protection System (RPS) when the reactor is critical, the licensee may, at its option, provide a telephone notification to the NRC Operations Center within 60 days after discovery of the event instead of submitting a written LER.'</br>On April 22, 2014, Comanche Peak Nuclear Power Plant Unit 2 was in Mode 5 during the 14th refueling outage. At approximately 0830 CDT, while performing a lockout test on EDG 2-01, the Reactor Operator made a place keeping error that resulted in EDG 2-01 starting and rolling up to approximately 300 RPM. The start signal should have been blocked as part of the test. However, a step was skipped due to a place keeping error and this resulted in an inadvertent start of EDG 2-01 during the performance of a subsequent step.</br>The specific train and system that actuated was the Unit 2, Train A, Emergency Diesel Generator. During the inadvertent EDG start the system started and functioned correctly, and the EDG only reached 300 RPM before it was shut down.</br>The licensee has notified the NRC Resident Inspector.e has notified the NRC Resident Inspector.  +
Has query"Has query" is a predefined property that represents meta information (in form of a <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Subobject">subobject</a>) about individual queries and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
00:00:00, 19 June 2014  +
Modification date"Modification date" is a predefined property that corresponds to the date of the last modification of a subject and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
22:19:52, 24 September 2017  +
15:19:00, 19 June 2014  +
false  +
58.076 d (1,393.82 hours, 8.297 weeks, 1.909 months)  +
13:30:00, 22 April 2014  +
Emergency Diesel Generator Invalid Actuation  +
URL"URL" is a <a href="/Special:Types/URL" title="Special:Types/URL">type</a> and predefined property provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a> to represent URI/URL values.
2  +