100  +
Reactor Building (Secondary Containment) pReactor Building (Secondary Containment) pressure rose above the Technical Specification Surveillance requirement of 0.25 inches vacuum water gauge multiple times from 0044 (PST) to 0305 (PST) on 2/17/14. The alarm was received in the control room at 0305 (PST). This is reportable as an event that could have prevented fulfillment of a safety function needed to control the release of radiation and mitigate the consequences of an accident. Reactor Building pressure has been restored to normal (greater than 0.25 inches of vacuum water gauge), returning Secondary Containment to operable status. Highest actual value indicated was +0.21 inches pressure water gauge. The cause of the event is under investigation.</br>There were no radiological releases associated with the event.</br>The NRC Resident Inspector has been notified. NRC Resident Inspector has been notified.  +
08:44:00, 17 February 2014  +
49,834  +
10:42:00, 17 February 2014  +
08:44:00, 17 February 2014  +
Reactor Building (Secondary Containment) pReactor Building (Secondary Containment) pressure rose above the Technical Specification Surveillance requirement of 0.25 inches vacuum water gauge multiple times from 0044 (PST) to 0305 (PST) on 2/17/14. The alarm was received in the control room at 0305 (PST). This is reportable as an event that could have prevented fulfillment of a safety function needed to control the release of radiation and mitigate the consequences of an accident. Reactor Building pressure has been restored to normal (greater than 0.25 inches of vacuum water gauge), returning Secondary Containment to operable status. Highest actual value indicated was +0.21 inches pressure water gauge. The cause of the event is under investigation.</br>There were no radiological releases associated with the event.</br>The NRC Resident Inspector has been notified. NRC Resident Inspector has been notified.  +
Has query"Has query" is a predefined property that represents meta information (in form of a <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Subobject">subobject</a>) about individual queries and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
100  +
00:00:00, 17 February 2014  +
Modification date"Modification date" is a predefined property that corresponds to the date of the last modification of a subject and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
01:51:42, 2 March 2018  +
10:42:00, 17 February 2014  +
false  +
0.0821 d (1.97 hours, 0.0117 weeks, 0.0027 months)  +
08:44:00, 17 February 2014  +
Loss of Secondary Containment Differential Pressure  +