Pressurizer Pressure LO Instrument surveilPressurizer Pressure LO Instrument surveillance testing was discovered to not have been completed as required. Existence of an internal jumper on solid state protection system input to logic cards prevented complete circuit testing. Unit 1 and unit 2 entered Technical Specification (TS) 3.0.3 at 1515 hours.</br>Alternate method of surveillance testing on one of the trains was completed and TS 3.0.3 was exited on Unit 1 at 2203 EDT and Unit 2 at 2132 EDT. The licensee plans to complete surveillance testing on the second train before 1515 hours on 9/27/12. The licensee is currently in TS 3.3.2.</br>The licensee has notified the NRC Resident Inspector. The states of North Carolina and South Carolina will be notified. Local county governments of York, Gaston, and Mecklenberg counties will also be notified.</br>* * * RETRACTION AT 1652 EDT ON 10/04/12 FROM AARON MICHALSKI TO HUFFMAN * * * </br>Catawba nuclear station is retracting EN #48348 for both units 1 and 2 based on completion of testing and investigation of system operability. The testing determined that both units respective train 'A' and 'B' pressurizer pressure low were operable and would have functioned as needed. This condition is not reportable under 10 CFR 50.72(b)(3)(ii)(B) and 10 CFR 50.72(b)(3)(v)(D). The licensee has notified the NRC Resident Inspector.</br>R2DO (O'Donohue) notified.dent Inspector. R2DO (O'Donohue) notified.  +
19:15:00, 26 September 2012  +
48,348  +
22:27:00, 26 September 2012  +
19:15:00, 26 September 2012  +
Pressurizer Pressure LO Instrument surveilPressurizer Pressure LO Instrument surveillance testing was discovered to not have been completed as required. Existence of an internal jumper on solid state protection system input to logic cards prevented complete circuit testing. Unit 1 and unit 2 entered Technical Specification (TS) 3.0.3 at 1515 hours.</br>Alternate method of surveillance testing on one of the trains was completed and TS 3.0.3 was exited on Unit 1 at 2203 EDT and Unit 2 at 2132 EDT. The licensee plans to complete surveillance testing on the second train before 1515 hours on 9/27/12. The licensee is currently in TS 3.3.2.</br>The licensee has notified the NRC Resident Inspector. The states of North Carolina and South Carolina will be notified. Local county governments of York, Gaston, and Mecklenberg counties will also be notified.</br>* * * RETRACTION AT 1652 EDT ON 10/04/12 FROM AARON MICHALSKI TO HUFFMAN * * * </br>Catawba nuclear station is retracting EN #48348 for both units 1 and 2 based on completion of testing and investigation of system operability. The testing determined that both units respective train 'A' and 'B' pressurizer pressure low were operable and would have functioned as needed. This condition is not reportable under 10 CFR 50.72(b)(3)(ii)(B) and 10 CFR 50.72(b)(3)(v)(D). The licensee has notified the NRC Resident Inspector.</br>R2DO (O'Donohue) notified.dent Inspector. R2DO (O'Donohue) notified.  +
Has query"Has query" is a predefined property that represents meta information (in form of a <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Subobject">subobject</a>) about individual queries and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
0.0175 d (0.421 hours, 0.0025 weeks, 5.764575e-4 months)  +
00:00:00, 4 October 2012  +
Modification date"Modification date" is a predefined property that corresponds to the date of the last modification of a subject and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
02:02:52, 2 March 2018  +
22:27:00, 26 September 2012  +
false  +
0.133 d (3.2 hours, 0.019 weeks, 0.00438 months)  +
true  +
19:15:00, 26 September 2012  +
Technical Specification 3.0.3 Entered Due to Surveillance Testing Not Being Completed as Required  +