Browse wiki

Jump to navigation Jump to search
100  +
Heating Steam condensate containing 9,430 Heating Steam condensate containing 9,430 picocuries per liter (pCi/L) of tritium overflowed from the Main Warehouse between November 22, 2011 and November 29, 2011. The US EPA drinking water limit for tritium is 20,000 pCi/L.</br>The Warehouse Condensate Return system failed to operate which resulted in the overflow of the Heating Steam condensate. There was a potential for the condensate to enter the environment where it could reach groundwater. The released volume for this event was conservatively calculated to be up to 3,900 gallons. The 122 Condensate Return Pump was replaced and the system was restored to service.</br>This voluntary report is in accordance with the Nuclear Energy Institute's Industry Ground Water Protection Initiative.</br>The licensee has notified the NRC Resident Inspector and will inform state and local agencies of this event.rm state and local agencies of this event.  +
13:58:00, 30 November 2011  +
47,629  +
12:49:00, 1 February 2012  +
13:58:00, 30 November 2011  +
Heating Steam condensate containing 9,430 Heating Steam condensate containing 9,430 picocuries per liter (pCi/L) of tritium overflowed from the Main Warehouse between November 22, 2011 and November 29, 2011. The US EPA drinking water limit for tritium is 20,000 pCi/L.</br>The Warehouse Condensate Return system failed to operate which resulted in the overflow of the Heating Steam condensate. There was a potential for the condensate to enter the environment where it could reach groundwater. The released volume for this event was conservatively calculated to be up to 3,900 gallons. The 122 Condensate Return Pump was replaced and the system was restored to service.</br>This voluntary report is in accordance with the Nuclear Energy Institute's Industry Ground Water Protection Initiative.</br>The licensee has notified the NRC Resident Inspector and will inform state and local agencies of this event.rm state and local agencies of this event.  +
Has query"Has query" is a predefined property that represents meta information (in form of a <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Subobject">subobject</a>) about individual queries and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
100  +
00:00:00, 1 February 2012  +
Modification date"Modification date" is a predefined property that corresponds to the date of the last modification of a subject and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
02:04:57, 2 March 2018  +
12:49:00, 1 February 2012  +
false  +
62.952 d (1,510.85 hours, 8.993 weeks, 2.07 months)  +
13:58:00, 30 November 2011  +
Offsite Notification Due to Unmonitored Release of Tritium (Heating Steam Condensate)  +
URL"URL" is a <a href="/Special:Types/URL" title="Special:Types/URL">type</a> and predefined property provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a> to represent URI/URL values.
1  +  and 2  +