During the 2000 CDT pumping of the DrywellDuring the 2000 CDT pumping of the Drywell Floor Drain Sump on 08/16/2008, the pumps failed to pump as indicated by the integrator reading zero with the pump running. The sump pump was running for approximately 2-3 minutes with the integrator showing no flow. The pump typically auto stops after approximately 30 seconds; since this did not happen, it appears to be a flow restriction and not an integrator problem. 3A DWFDS pump was started first and then 3B DWFDS pump was attempted with no flow noted for either pump.</br>Both the 3-2001-105 and -106 valves indicated OPEN. Both sump pump breakers were verified ON and a local visual inspection of the 3-2001-105 and -106 valves was performed to verify proper operation. Troubleshooting has determined that the 3-2001-105 valve is failing to OPEN.</br>The 3-2001-105 is a primary containment isolation valve and is currently CLOSED.</br>TS SR 3.4.4.1 requires RCS leakage verification 1 (time per) 12 hours and was last completed at 1600 CDT on 08/16/2008.</br>Unit 3 Shutdown was initiated at 0902 hours.</br>The shutdown of Unit 3 was halted at 30% power while the licensee pursued an NOED (Notice of Enforcement Discretion) with NRC.</br>The NRC Resident Inspector has been notified. The licensee will also notified the State.The licensee will also notified the State.  +
14:02:00, 17 August 2008  +
13:11:00, 17 August 2008  +
14:02:00, 17 August 2008  +
During the 2000 CDT pumping of the DrywellDuring the 2000 CDT pumping of the Drywell Floor Drain Sump on 08/16/2008, the pumps failed to pump as indicated by the integrator reading zero with the pump running. The sump pump was running for approximately 2-3 minutes with the integrator showing no flow. The pump typically auto stops after approximately 30 seconds; since this did not happen, it appears to be a flow restriction and not an integrator problem. 3A DWFDS pump was started first and then 3B DWFDS pump was attempted with no flow noted for either pump.</br>Both the 3-2001-105 and -106 valves indicated OPEN. Both sump pump breakers were verified ON and a local visual inspection of the 3-2001-105 and -106 valves was performed to verify proper operation. Troubleshooting has determined that the 3-2001-105 valve is failing to OPEN.</br>The 3-2001-105 is a primary containment isolation valve and is currently CLOSED.</br>TS SR 3.4.4.1 requires RCS leakage verification 1 (time per) 12 hours and was last completed at 1600 CDT on 08/16/2008.</br>Unit 3 Shutdown was initiated at 0902 hours.</br>The shutdown of Unit 3 was halted at 30% power while the licensee pursued an NOED (Notice of Enforcement Discretion) with NRC.</br>The NRC Resident Inspector has been notified. The licensee will also notified the State.The licensee will also notified the State.  +
Has query"Has query" is a predefined property that represents meta information (in form of a <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Subobject">subobject</a>) about individual queries and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
1.388889e-4 d (0.00333 hours, 1.984127e-5 weeks, 4.566e-6 months)  +  and 0.0104 d (0.251 hours, 0.00149 weeks, 3.43211e-4 months)  +
00:00:00, 17 August 2008  +
Modification date"Modification date" is a predefined property that corresponds to the date of the last modification of a subject and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
02:13:51, 2 March 2018  +
13:11:00, 17 August 2008  +
false  +
-0.0354 d (-0.85 hours, -0.00506 weeks, -0.00116 months)  +
14:02:00, 17 August 2008  +
Technical Specification Shutdown Due to Inabililty to Perform a Required Rcs Leak Rate Verification  +