Browse wiki

Jump to navigation Jump to search
This 60-day optional telephone notificatioThis 60-day optional telephone notification as allowed by 10 CFR 50.73(a)(1) is being made in lieu of an LER submittal. This notification is made pursuant to the reporting requirements specified in 10 CFR50.73(a)(2)(iv)(A) for an invalid actuation of one of the systems listed in 10 CFR 50.73(a)(2)(iv)(B).</br>On October 14, 2007, at approximately 0200 hours EST with the plant in Mode 5, Refueling, while performing ECCS Start and Load Reject surveillance testing on Emergency Diesel Generator (EDG) 14, the EDG unexpectedly auto-started. Investigation revealed that the auto-start was caused by a faulty test switch. The test switch had been tested multiple times prior to performing the surveillance with no abnormalities noted. </br>EDG 14 is one of two EDG's in Division II of the Onsite Emergency Power system. The EDG responded properly to the auto-start signal. The actuation was complete, in that the EDG started and ran unloaded. The surveillance testing was immediately stopped upon receipt of the inadvertent actuation. In accordance with the EDG operating procedure, the EDG was synchronized, loaded for about an hour, shut down and returned to standby status.</br>Since no actual plant condition existed that required the EDG to auto-start, the actuation was invalid. There were no safety consequences or impact on the health and safety of the public. The event was entered in the corrective action program for evaluation and resolution.</br>The NRC Resident Inspector will be notified of this report.Inspector will be notified of this report.  +
07:00:00, 14 October 2007  +
43,840  +
17:02:00, 12 December 2007  +
07:00:00, 14 October 2007  +
This 60-day optional telephone notificatioThis 60-day optional telephone notification as allowed by 10 CFR 50.73(a)(1) is being made in lieu of an LER submittal. This notification is made pursuant to the reporting requirements specified in 10 CFR50.73(a)(2)(iv)(A) for an invalid actuation of one of the systems listed in 10 CFR 50.73(a)(2)(iv)(B).</br>On October 14, 2007, at approximately 0200 hours EST with the plant in Mode 5, Refueling, while performing ECCS Start and Load Reject surveillance testing on Emergency Diesel Generator (EDG) 14, the EDG unexpectedly auto-started. Investigation revealed that the auto-start was caused by a faulty test switch. The test switch had been tested multiple times prior to performing the surveillance with no abnormalities noted. </br>EDG 14 is one of two EDG's in Division II of the Onsite Emergency Power system. The EDG responded properly to the auto-start signal. The actuation was complete, in that the EDG started and ran unloaded. The surveillance testing was immediately stopped upon receipt of the inadvertent actuation. In accordance with the EDG operating procedure, the EDG was synchronized, loaded for about an hour, shut down and returned to standby status.</br>Since no actual plant condition existed that required the EDG to auto-start, the actuation was invalid. There were no safety consequences or impact on the health and safety of the public. The event was entered in the corrective action program for evaluation and resolution.</br>The NRC Resident Inspector will be notified of this report.Inspector will be notified of this report.  +
Has query"Has query" is a predefined property that represents meta information (in form of a <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Subobject">subobject</a>) about individual queries and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
0.00231 d (0.0556 hours, 3.306878e-4 weeks, 7.61e-5 months)  +
00:00:00, 12 December 2007  +
Modification date"Modification date" is a predefined property that corresponds to the date of the last modification of a subject and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
02:15:26, 2 March 2018  +
17:02:00, 12 December 2007  +
false  +
59.376 d (1,425.03 hours, 8.482 weeks, 1.952 months)  +
07:00:00, 14 October 2007  +
Inadvertent Actuation of Emergency Diesel Generator  +
URL"URL" is a <a href="/Special:Types/URL" title="Special:Types/URL">type</a> and predefined property provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a> to represent URI/URL values.
2  +