Browse wiki

Jump to navigation Jump to search
100  +
During surveillance testing of 1R43S001B EDuring surveillance testing of 1R43S001B Emergency Diesel Generator 1B (swing EDG) from Unit 2 controls, 1R24S026 EDG 1 B Motor Control Center (MCC) did not transfer from Unit 1 power supply to Unit 2 power supply resulting in 1R24S026 being de-energized. MCC 1R24S026 provides power to Technical Support Center (TSC) HVAC which resulted in TSC HVAC being inoperable. Corrective work activities are in progress to expeditiously return the TSC HVAC back to service.</br>If an emergency condition requiring activation of the Technical Support Center (TSC) occurs during the time the HVAC is inoperable, then contingency plans call for utilization of the TSC as long as radiological conditions allow. The Technical Support Center Activation procedure provides instructions to direct TSC management to the Control Room and TSC support personnel to the Simulator Building to continue TSC activities if it is necessary to relocate from the TSC so that TSC functions can be continued.</br>The licensee notified the NRC Resident Inspector.ensee notified the NRC Resident Inspector.  +
13:43:00, 1 June 2006  +
42,613  +
12:33:00, 1 June 2006  +
13:43:00, 1 June 2006  +
During surveillance testing of 1R43S001B EDuring surveillance testing of 1R43S001B Emergency Diesel Generator 1B (swing EDG) from Unit 2 controls, 1R24S026 EDG 1 B Motor Control Center (MCC) did not transfer from Unit 1 power supply to Unit 2 power supply resulting in 1R24S026 being de-energized. MCC 1R24S026 provides power to Technical Support Center (TSC) HVAC which resulted in TSC HVAC being inoperable. Corrective work activities are in progress to expeditiously return the TSC HVAC back to service.</br>If an emergency condition requiring activation of the Technical Support Center (TSC) occurs during the time the HVAC is inoperable, then contingency plans call for utilization of the TSC as long as radiological conditions allow. The Technical Support Center Activation procedure provides instructions to direct TSC management to the Control Room and TSC support personnel to the Simulator Building to continue TSC activities if it is necessary to relocate from the TSC so that TSC functions can be continued.</br>The licensee notified the NRC Resident Inspector.ensee notified the NRC Resident Inspector.  +
Has query"Has query" is a predefined property that represents meta information (in form of a <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Subobject">subobject</a>) about individual queries and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
100  +
00:00:00, 1 June 2006  +
Modification date"Modification date" is a predefined property that corresponds to the date of the last modification of a subject and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
22:38:42, 24 September 2017  +
12:33:00, 1 June 2006  +
false  +
-0.0488 d (-1.17 hours, -0.00696 weeks, -0.0016 months)  +
13:43:00, 1 June 2006  +
Technical Support Center Hvac Inoperable  +
URL"URL" is a <a href="/Special:Types/URL" title="Special:Types/URL">type</a> and predefined property provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a> to represent URI/URL values.
1  +  and 2  +