Browse wiki

Jump to navigation Jump to search
At 0953 (CDT) on 04/13/2005 with Unit 2 inAt 0953 (CDT) on 04/13/2005 with Unit 2 in MODE 4 (and) all Control Rods inserted, a valid RPS Actuation (Reactor SCRAM Signal resulting from the filling of the SCRAM DISCHARGE VOLUME) was received as a result of an invalid ATWS initiation. This occurred during the performance of 2-SR-3.3.5.2.4(FT) RCIC SYSTEM LOGIC FUNCTIONAL TEST. Further review of the test revealed that a Volt/Ohm Meter was attached across contacts in the ATWS LOGIC that conflicted with the RCIC Surveillance and apparently resulted in the ATWS initiation and the filling of the SCRAM DISCHARGE VOLUME.</br>This event is reportable as an 8-hour Non-Emergency Notification along with a 60-day written report in accordance with 10CFR50.72 (b)(3)(iv)(A) & 10CFR50.73(a)(2)(iv)(A) as 'Any event or condition that results in valid actuation of RPS & PCIS as described in (1) & (2) below.' </br>The licensee notified the NRC Resident Inspector.w.' The licensee notified the NRC Resident Inspector.  +
15:53:00, 13 April 2005  +
41,595  +
18:19:00, 13 April 2005  +
15:53:00, 13 April 2005  +
At 0953 (CDT) on 04/13/2005 with Unit 2 inAt 0953 (CDT) on 04/13/2005 with Unit 2 in MODE 4 (and) all Control Rods inserted, a valid RPS Actuation (Reactor SCRAM Signal resulting from the filling of the SCRAM DISCHARGE VOLUME) was received as a result of an invalid ATWS initiation. This occurred during the performance of 2-SR-3.3.5.2.4(FT) RCIC SYSTEM LOGIC FUNCTIONAL TEST. Further review of the test revealed that a Volt/Ohm Meter was attached across contacts in the ATWS LOGIC that conflicted with the RCIC Surveillance and apparently resulted in the ATWS initiation and the filling of the SCRAM DISCHARGE VOLUME.</br>This event is reportable as an 8-hour Non-Emergency Notification along with a 60-day written report in accordance with 10CFR50.72 (b)(3)(iv)(A) & 10CFR50.73(a)(2)(iv)(A) as 'Any event or condition that results in valid actuation of RPS & PCIS as described in (1) & (2) below.' </br>The licensee notified the NRC Resident Inspector.w.' The licensee notified the NRC Resident Inspector.  +
Has query"Has query" is a predefined property that represents meta information (in form of a <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Subobject">subobject</a>) about individual queries and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
00:00:00, 13 April 2005  +
Modification date"Modification date" is a predefined property that corresponds to the date of the last modification of a subject and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
02:21:15, 2 March 2018  +
18:19:00, 13 April 2005  +
false  +
false  +
0.101 d (2.43 hours, 0.0145 weeks, 0.00333 months)  +
15:53:00, 13 April 2005  +
Valid Rps Actuation Due to an Invalid Atws Logic Actuation  +
URL"URL" is a <a href="/Special:Types/URL" title="Special:Types/URL">type</a> and predefined property provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a> to represent URI/URL values.
2  +