Browse wiki

Jump to navigation Jump to search
100  +
On 08/13/2004 at 1030 CDT the Kewaunee ShiOn 08/13/2004 at 1030 CDT the Kewaunee Shift Manager was notified the control room emergency zone (CREZ) boundary was outside assumed design basis for an unknown amount of time. This is an eight hour non-emergency reportable under 10 CFR 50.72(b)(3)(v)(D), Accident Mitigation.</br>On 08/12/2004 at 1915 (CDT), the local operator reported to the control room that he found a control room emergency zone (CREZ) boundary door in the unlatched open position. The local operator immediately ensured the door was secured in the latched closed position. Per Kewaunee's barrier control procedure the Shift Manager requested an evaluation be performed to determine the impact of potential air in leakage on the control room post accident dose consequences.</br>On 08/13/2004 at 1030 CDT, the engineering staff reported that based on engineering judgment the unfiltered in leakage that could have entered the CREZ would likely exceed that assumed in the post accident dose analysis. Based on this judgment, the in leakage would have prevented the Control Room Post Accident Recirculation System from mitigating the dose consequences to the control room staff to values less than those determined in accident analysis.</br>At the time of discovery the local operator immediately secured the boundary door rendering the CREZ boundary operable. This event has been entered in the Kewaunee corrective action process to investigate the cause of the door being in the open position. No other safety related equipment was out of service at the time of discovery.</br>The licensee has notified the NRC Resident Inspector.e has notified the NRC Resident Inspector.  +
15:30:00, 13 August 2004  +
40,950  +
15:23:00, 13 August 2004  +
15:30:00, 13 August 2004  +
On 08/13/2004 at 1030 CDT the Kewaunee ShiOn 08/13/2004 at 1030 CDT the Kewaunee Shift Manager was notified the control room emergency zone (CREZ) boundary was outside assumed design basis for an unknown amount of time. This is an eight hour non-emergency reportable under 10 CFR 50.72(b)(3)(v)(D), Accident Mitigation.</br>On 08/12/2004 at 1915 (CDT), the local operator reported to the control room that he found a control room emergency zone (CREZ) boundary door in the unlatched open position. The local operator immediately ensured the door was secured in the latched closed position. Per Kewaunee's barrier control procedure the Shift Manager requested an evaluation be performed to determine the impact of potential air in leakage on the control room post accident dose consequences.</br>On 08/13/2004 at 1030 CDT, the engineering staff reported that based on engineering judgment the unfiltered in leakage that could have entered the CREZ would likely exceed that assumed in the post accident dose analysis. Based on this judgment, the in leakage would have prevented the Control Room Post Accident Recirculation System from mitigating the dose consequences to the control room staff to values less than those determined in accident analysis.</br>At the time of discovery the local operator immediately secured the boundary door rendering the CREZ boundary operable. This event has been entered in the Kewaunee corrective action process to investigate the cause of the door being in the open position. No other safety related equipment was out of service at the time of discovery.</br>The licensee has notified the NRC Resident Inspector.e has notified the NRC Resident Inspector.  +
Has query"Has query" is a predefined property that represents meta information (in form of a <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Subobject">subobject</a>) about individual queries and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
100  +
00:00:00, 13 August 2004  +
Modification date"Modification date" is a predefined property that corresponds to the date of the last modification of a subject and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
22:42:46, 24 September 2017  +
15:23:00, 13 August 2004  +
false  +
-0.005 d (-0.12 hours, -7.142857e-4 weeks, -1.64376e-4 months)  +
15:30:00, 13 August 2004  +
Control Room Emergency Zone Boundary Outside Design Basis  +