Browse wiki

Jump to navigation Jump to search
At 0941 CST on 1/30/04, the Plant Shift SuAt 0941 CST on 1/30/04, the Plant Shift Superintendent (PSS) was notified that High Pressure Fire Water System, C-1, in C-333 building was discovered to be in a potential frozen condition on the system main supply header standpipe. Frozen water in the standpipe could result in the restricted flow or complete loss of water supply to the sprinkler heads. The PSS declared the system inoperable and TSR LCO 2.4.4.5 actions were initiated to remove the system from service. </br>Freeze out of the system was due to extremely low outside ambient temperatures and a faulty filter room thermostat. The event is reportable as a 24 hour event, as required by 10 CFR 76.120(c)(2)(i); An event in which equipment is disabled or fails to function as designed when the equipment is required by a TSR to prevent releases, prevent exposures to radiation and radioactive materials exceeding specified limits, mitigate the consequences of an accident, or restore this facility to a pre-established safe condition after an accident. The equipment was required by TSR to be available and operable and no redundant equipment was available to perform the required safety function.</br>The faulty filter room thermostat was replaced, and the High Pressure Fire Water System was declared operable at 1500 CST. Operations personnel took compensatory measures by checking similar indicators in all process buildings.</br>The Senior NRC Resident Inspector has been notified of this event.Inspector has been notified of this event.  +
15:41:00, 30 January 2004  +
40,492  +
18:40:00, 30 January 2004  +
15:41:00, 30 January 2004  +
At 0941 CST on 1/30/04, the Plant Shift SuAt 0941 CST on 1/30/04, the Plant Shift Superintendent (PSS) was notified that High Pressure Fire Water System, C-1, in C-333 building was discovered to be in a potential frozen condition on the system main supply header standpipe. Frozen water in the standpipe could result in the restricted flow or complete loss of water supply to the sprinkler heads. The PSS declared the system inoperable and TSR LCO 2.4.4.5 actions were initiated to remove the system from service. </br>Freeze out of the system was due to extremely low outside ambient temperatures and a faulty filter room thermostat. The event is reportable as a 24 hour event, as required by 10 CFR 76.120(c)(2)(i); An event in which equipment is disabled or fails to function as designed when the equipment is required by a TSR to prevent releases, prevent exposures to radiation and radioactive materials exceeding specified limits, mitigate the consequences of an accident, or restore this facility to a pre-established safe condition after an accident. The equipment was required by TSR to be available and operable and no redundant equipment was available to perform the required safety function.</br>The faulty filter room thermostat was replaced, and the High Pressure Fire Water System was declared operable at 1500 CST. Operations personnel took compensatory measures by checking similar indicators in all process buildings.</br>The Senior NRC Resident Inspector has been notified of this event.Inspector has been notified of this event.  +
Has query"Has query" is a predefined property that represents meta information (in form of a <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Subobject">subobject</a>) about individual queries and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
2.777778e-4 d (0.00667 hours, 3.968254e-5 weeks, 9.132e-6 months)  +
00:00:00, 30 January 2004  +
GDP-1  +
Modification date"Modification date" is a predefined property that corresponds to the date of the last modification of a subject and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
23:42:12, 24 November 2018  +
18:40:00, 30 January 2004  +
0.124 d (2.98 hours, 0.0177 weeks, 0.00408 months)  +
15:41:00, 30 January 2004  +
Safety Equipment Failure  +
URL"URL" is a <a href="/Special:Types/URL" title="Special:Types/URL">type</a> and predefined property provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a> to represent URI/URL values.