Browse wiki

Jump to navigation Jump to search
The team identified a Green non-cited violThe team identified a Green non-cited violation of License Conditions 2.C.7, 2.C.6, and 2.F for Units 1, 2, and 3, respectively, because the licensee had not established criteria for determining when a fire main loop had degraded and had not properly tested all portions of the fire main loop. Specifically, the licensee had not established a differential pressure that would initiate actions to evaluate the cause for a degradation and the licensee had not determined the flow through individual flow paths in their auxiliary and control buildings. The licensee documented these issues in Condition Reports 15-00513 and 16-00686 and initiated actions to correct the procedure and perform the flow test of the individual loops. The team identified a performance deficiency related to the procedure used to test their fire main loop. Specifically, the licensee had not established criteria for determining a degraded fire main loop and had not properly tested all portions of the fire main loop. This performance deficiency was more than minor because it was associated with the protection against external factors attribute (fire) and adversely affected the Mitigating Systems Cornerstone objective to ensure the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. Specifically, the failure to test the fire main loops inside the control/auxiliary building separately and failure to establish appropriate acceptance criteria affected the ability to demonstrate the continued capability to deliver adequate flow and pressure to the fire suppression systems. The finding was screened in accordance with NRC Inspection Manual Chapter (IMC) 0609, Significance Determination Process, Attachment 4, Initial Characterization of Findings, dated June 19, 2012. The inspectors determined that an IMC 0609, Appendix F, Fire Protection Significance Determination Process, dated September 20, 2013, review was required as the finding affected the ability to reach and maintain safe shutdown conditions in case of a fire. Using IMC 0609, Appendix F, Attachment 1, Fire Protection Significance Determination Process Worksheet, dated September 20, 2013, the finding was screened as a Green finding of very low safety significance in accordance with Task 1.4.7, Fire Water Supply, Question A. The inspectors determined that although the licensee failed to test portions of the fire main system in accordance with code requirements, the inspectors determined that at least 50 percent of required fire water capacity would be available based on the testing is done with only one fire pump in service and there are three available fire pumps. Since these fire main loops inside the control/auxiliary building had not been monitored for pressure changes when flow tested since initial testing and nothing caused the licensee to reevaluate the test, the team determined that this failure did not reflect current performance.ilure did not reflect current performance.  
23:59:59, 31 March 2016  +
05000528  +, 05000529  +  and 05000530  +
23:59:59, 31 March 2016  +
Has query"Has query" is a predefined property that represents meta information (in form of a <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Subobject">subobject</a>) about individual queries and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
Modification date"Modification date" is a predefined property that corresponds to the date of the last modification of a subject and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
12:56:35, 25 September 2017  +
23:59:59, 31 March 2016  +
Inadequate Flow Test Procedure  +