The inspectors identified a non-cited viol … The inspectors identified a non-cited violation of Technical Specification 5.4.1.a, Procedures, for maintenance instructions inappropriate to the circumstances. Specifically, Work Orders 11-341986-005 and 11-342065-002 did not contain adequate instructions for reassembling essential service water Garlock expansion joints to ensure proper joint alignment. As a result, on February 11, 2014, the inspectors identified that the inlet expansion joint for the essential service water intercooler heat exchanger, which provides cooling to emergency diesel generator B jacket water system, was misaligned by 0.5 inches, which exceeded the vendor specification of less than 0.125 inch. This item was entered into the corrective action program as Condition Reports 79352 and 79623, and the fitting was replaced during the mid-cycle 2014 outage. The licensee also conducted an extent of condition inspection and identified three additional Garlock expansion joints that were not made with the approved liner material. The failure to properly reinstall essential service water expansion joints consistent with the vendor approved and analyzed configuration was a performance deficiency. The performance deficiency is more than minor because it affected the equipment performance attribute of the Mitigating Systems Cornerstone objective to ensure the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. Specifically, the misaligned Garlock expansion joint in the essential service water system degraded its long-term operability and its ability to withstand a seismic event. Using the Inspection Manual Chapter 0609, Appendix A, Exhibit 2, Mitigating Systems Screening Questions, the inspectors determined that the finding was of very low safety significance (Green) because the finding did not represent an actual loss of function of at least a single train for greater than its technical specification allowed outage time and the finding did not represent an actual loss of function of one or more non-technical specification trains of equipment designated as high safety-significant in accordance with the licensees Maintenance Rule program for greater than 24 hours. Specifically, although the expansion joint was in a degraded condition, it was determined to be operable based on an engineering evaluation and seismic test data. The inspectors determined that the finding had a cross-cutting aspect in the human performance area of resources because the licensee did not ensure that personnel equipment, procedures, and other resources were available and adequate to support nuclear safety.le and adequate to support nuclear safety.
23:59:59, 31 March 2014 +
23:59:59, 31 March 2014 +
Has query"Has query" is a predefined property that represents meta information (in form of a <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Subobject">subobject</a>) about individual queries and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
05000482/FIN-2014002-01 +, 05000482/FIN-2014002-01 +, 05000482/FIN-2014002-01 +, 05000482/FIN-2014002-01 +, 05000482/FIN-2014002-01 +, 05000482/FIN-2014002-01 +, 05000482/FIN-2014002-01 +, 05000482/FIN-2014002-01 +, 05000482/FIN-2014002-01 +, 05000482/FIN-2014002-01 +, 05000482/FIN-2014002-01 +, 05000482/FIN-2014002-01 +, 05000482/FIN-2014002-01 +, 05000482/FIN-2014002-01 +, 05000482/FIN-2014002-01 +, 05000482/FIN-2014002-01 +, 05000482/FIN-2014002-01 +, 05000482/FIN-2014002-01 +, 05000482/FIN-2014002-01 +, 05000482/FIN-2014002-01 +, 05000482/FIN-2014002-01 +, 05000482/FIN-2014002-01 +, 05000482/FIN-2014002-01 +, 05000482/FIN-2014002-01 +, 05000482/FIN-2014002-01 +, 05000482/FIN-2014002-01 +, 05000482/FIN-2014002-01 +, 05000482/FIN-2014002-01 +, 05000482/FIN-2014002-01 +, 05000482/FIN-2014002-01 +...
N O'Keefe +, P Hernandez +, R Stroble +, L Ricketson +, David Proulx +, Peter Jayroe +, Charley Peabody +, Gary Callaway + and David You +
Modification date"Modification date" is a predefined property that corresponds to the date of the last modification of a subject and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
04:21:00, 22 February 2018 +
N O'Keefe +, P Hernandez +, R Stroble +, L Ricketson +, David Proulx +, Peter Jayroe +, Charley Peabody +, Gary Callaway + and David You +
23:59:59, 31 March 2014 +