Browse wiki

Jump to navigation Jump to search
The inspectors identified a noncited violaThe inspectors identified a noncited violation of 10 CFR 50 Appendix B, Criterion III, Design Control for the failure to consider the temperature effect on the pressurization of safety-related air accumulators for containment isolation valves in the main steam line penetration room. As a result, the accumulators could exceed their design pressure during a steam line break. The licensee entered the finding into the corrective action program as Condition Report CR-2010-006349. The finding was more than minor because it was associated with the design control attribute of the barrier integrity cornerstone and adversely affected the cornerstone objective to provide reasonable assurance that physical barriers protect the public from radionuclide releases caused by events. Using NRC Manual Chapter 0609, Attachment 4, Phase 1 - Initial Screening and Characterization of Findings, the finding was determined to be of very low safety significance because the finding did not result in an actual open pathway in the physical integrity of reactor containment. The finding did not have a crosscutting aspect because the performance deficiency was not representative of current licensee performance (Section 1R04).rrent licensee performance (Section 1R04).  +
23:59:59, 30 September 2010  +
05000445  +  and 05000446  +
23:59:59, 30 September 2010  +
Has query"Has query" is a predefined property that represents meta information (in form of a <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Subobject">subobject</a>) about individual queries and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
Modification date"Modification date" is a predefined property that corresponds to the date of the last modification of a subject and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
21:52:32, 8 October 2017  +
23:59:59, 30 September 2010  +
Failure to Consider Temperature Effects on Air Accumulator Overpressure Protection  +