Browse wiki

Jump to navigation Jump to search
Green . The inspectors identified a findinGreen . The inspectors identified a finding of very-low safety significance with an associated NCV of Title 10 of the Code of Federal Regulations (CFR) , Part 50, Appendix B, Criterion V, Instructions, Procedures, and Drawings, because the licensee failed to establish a procedure that ensured the American Society of Mechanical Engineers (ASME) Code VT 3 examination of the internal surface of valves or pumps occurred in the as -found condition (e.g., prior to repairs). Consequently, the licensee repaired internal damage to the 2B33 F067B valve prior to the Code VT 3 examination which potentially resulted in an ineffective VT 3 examination. The licensee entered this issue into their corrective action program (CAP) as Action Request (AR) 3972620, initiated actions to complete another VT 3 examination of valve 2B33 F067A or valve 2B33 F067B during the current outage and was evaluating additional controls for scheduling VT 3 internal examinations of pumps and valves. The performance deficiency was determined to be more- than- minor because it affected the Initiating Events cornerstone attribute of equipment performance and adversely affected the cornerstone objective to l imit the likelihood of events that upset plant stability and challenge critical safety functions during shutdown as well as power operations. Specifically, if left uncorrected, this finding would lead to a more significant safety concern because it increa sed the likelihood of an operational challenge to the plant caused by a recirculation system line break initiated from undetected service -induced defects left in service inside pumps or valves as a result of ineffective VT 3 examinations. The finding was screened in accordance with Inspection Manual Chapter 0609, Appendix A, and the inspectors answered No to the applicable Phase 1 Initiating Events Screening question because the finding did not result in a reactor trip and/or loss of mitigation equipment relied upon to transition the plant from the onset of the trip to a stable shutdown condition. Therefore, this finding was determined to have very- low safety significance (Green) . The finding had a cross -cutting aspect of Work Management in the Human Performance cross -cutting area because licensee managers failed to establish an adequate process of planning, controlling, and executing 3 work activities such that nuclear safety is the overriding priority as evidenced by the lack of appropriately controls for scheduling the VT 3 internal examination of the 2B33 F067B valve (H.5)examination of the 2B33 F067B valve (H.5)  
23:59:59, 31 March 2017  +
05000373  +  and 05000374  +
23:59:59, 31 March 2017  +
Has query"Has query" is a predefined property that represents meta information (in form of a <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Subobject">subobject</a>) about individual queries and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
Modification date"Modification date" is a predefined property that corresponds to the date of the last modification of a subject and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
12:58:10, 25 September 2017  +
23:59:59, 31 March 2017  +
nadequate Controls for ASME Code VT 3 Internal Examination of Pumps and Valves  +