Browse wiki

Jump to navigation Jump to search
A self-revealing finding was identified foA self-revealing finding was identified for the licensees failure to implement adequate instructions for venting condensate booster pump (CBP) emergency low suction pressure trip instrumentation which resulted in air entrainment causing a non-conservative shift in the trip setpoint. During a subsequent secondary side transient involving a heater drain tank pump trip, the non-conservative trip setpoint resulted in a premature trip of all three CBPs ultimately causing a reactor trip. The performance deficiency was more than minor because it affected the Procedure Quality attribute of the Initiating Events Cornerstone and adversely affected the cornerstone objective, in that, the inadequate venting allowed air entrainment in the instrumentation lines resulting in a reactor trip. This finding was determined to have very low safety significance (Green) because it did not contribute to the likelihood of both a reactor trip and that mitigation equipment or functions would not be available. No cross cutting aspect was identified.e. No cross cutting aspect was identified.  +
23:59:59, 30 June 2013  +
05000369  +  and 05000370  +
23:59:59, 30 June 2013  +
Has query"Has query" is a predefined property that represents meta information (in form of a <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Subobject">subobject</a>) about individual queries and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
Modification date"Modification date" is a predefined property that corresponds to the date of the last modification of a subject and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
00:48:36, 21 February 2018  +
23:59:59, 30 June 2013  +
Failure to Implement Adequate Venting Instructions for Condensate Booster Pump Trip Instrumentation Resulting in Reactor Trip  +