Browse wiki

Jump to navigation Jump to search
The inspectors identified a finding of verThe inspectors identified a finding of very low safety significance and associated Severity Level IV violation of 10 CFR 50.59, Changes, Tests, and Experiments, for the failure to perform a written evaluation, which provided the bases for the determination that a change did not require a license amendment. Specifically, the licensee failed to provide a basis for not applying for a license amendment associated with a modification of the residual heat removal pump casing drain lines. The finding was entered into the licensees corrective action program to: (1) stage a hose and pipe couplings to support venting at the residual heat removal pump casing vent; (2) create a work order request to flush flow through the abandoned drain lines that were cut from the pump casing vent to show the lines could still pass water; (3) develop an alternate means to accomplish this activity; and (4) evaluate the change. The performance deficiency was determined to be more than minor because it was associated with the Mitigating System cornerstone attribute of equipment performance and affected the cornerstone objective of ensuring the capability and availability of systems that respond to initiating events to prevent undesirable consequences. Violations of 10 CFR 50.59 are dispositioned using the traditional enforcement process instead of the significance determination process because they are considered to be violations that potentially impede or impact the regulatory process. The finding screened as of very low safety significance (Green) using a Phase II evaluation. The inspectors did not identify a cross-cutting aspect associated with this finding because the finding was not confirmed to reflect current performance due to the age of the performance deficiency. to the age of the performance deficiency.  +
23:59:59, 30 September 2012  +
05000315  +  and 05000316  +
23:59:59, 30 September 2012  +
Has query"Has query" is a predefined property that represents meta information (in form of a <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Subobject">subobject</a>) about individual queries and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
Modification date"Modification date" is a predefined property that corresponds to the date of the last modification of a subject and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
00:47:34, 21 February 2018  +
23:59:59, 30 September 2012  +
10 CFR 50.59 evaluation for modification of RHR pump casing drain lines was not performed  +