Browse wiki
Jump to navigation
Jump to search
The team identified seven examples of a Gr … The team identified seven examples of a Green noncited violation of 10 CFR Part 50, Appendix B, Criterion III, Design Control, for failure to establish measures to ensure that applicable regulatory requirements and the design bases were correctly translated into specifications, drawings, procedures, and instructions. These measures shall include provisions to ensure that appropriate quality standards are specified and included in design documents and that deviations from such standards are controlled. Specifically, as of August 12, 2010, the licensee failed to correctly translate regulatory requirements and design bases information into specifications, drawings, procedures, and instructions involving emergency diesel generator frequency, service water pump, electrical cables for the residual heat removal pumps, seismic supports, the emergency diesel generator air start system testing, tornado and high wind impact on the emergency diesel generator fuel oil storage facilities and safety-related Agast relay service life evaluations. This finding was entered into the licensees corrective action program as Condition Reports CNS-2010-05301, CNS-2010-5763, CNS-2010-05222, CNS-2010-05281, CNS-2010-5294, CNS-2010-5350, and CNS-2010-5438. The failure to correctly translate regulatory requirements and design bases information into specifications, drawings, procedures, and instructions for the emergency diesel generator frequency, service water pump, electrical cables for the residual heat removal pumps, emergency diesel generator room ventilation seismic supports, emergency diesel generator air start system testing, tornado and high wind impact on the emergency diesel generator fuel oil storage facilities and safety-related Agast relay service life evaluations was a performance deficiency. This finding was more than minor because it was associated with the design control attribute of the mitigating systems cornerstone and impacted the cornerstone objective to ensure the availability, reliability, and capability of the affected system to respond to events and prevent undesirable consequences. Using the Manual Chapter 0609, Attachment 4, Phase 1 Initial Screening and Characterization of Findings, the issue screened as having very low safety significance (Green) because it was not a design or qualification deficiency and did not represent a loss of safety function. The licensee performed evaluations which determined that the affected components and systems were capable of meeting their design functions. The finding had a crosscutting aspect in the area of problem identification and resolution, associated with operating experience because the licensee failed to properly evaluate and apply various industry events associated with the above systems and incorporate the information into plant procedures and training.mation into plant procedures and training.
23:59:59, 31 December 2010 +
23:59:59, 31 December 2010 +
Has query"Has query" is a predefined property that represents meta information (in form of a <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Subobject">subobject</a>) about individual queries and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
05000298/FIN-2010007-04 +, 05000298/FIN-2010007-04 +, 05000298/FIN-2010007-04 +, 05000298/FIN-2010007-04 +, 05000298/FIN-2010007-04 +, 05000298/FIN-2010007-04 +, 05000298/FIN-2010007-04 +, 05000298/FIN-2010007-04 +, 05000298/FIN-2010007-04 +, 05000298/FIN-2010007-04 +, 05000298/FIN-2010007-04 +, 05000298/FIN-2010007-04 +, 05000298/FIN-2010007-04 +, 05000298/FIN-2010007-04 +, 05000298/FIN-2010007-04 +, 05000298/FIN-2010007-04 +, 05000298/FIN-2010007-04 +, 05000298/FIN-2010007-04 +, 05000298/FIN-2010007-04 +, 05000298/FIN-2010007-04 +, 05000298/FIN-2010007-04 +, 05000298/FIN-2010007-04 +, 05000298/FIN-2010007-04 +, 05000298/FIN-2010007-04 +, 05000298/FIN-2010007-04 + and 05000298/FIN-2010007-04 +
Modification date"Modification date" is a predefined property that corresponds to the date of the last modification of a subject and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
21:44:50, 8 October 2017 +
23:59:59, 31 December 2010 +