Browse wiki

Jump to navigation Jump to search
The inspectors identified a Non-Cited ViolThe inspectors identified a Non-Cited Violation (NCV) of 10 CFR Part 50,Appendix B, Criterion XVI, Corrective Actions, for the failure to promptly correct a condition adverse to quality regarding the expired qualification of safety-related molded case circuit breakers. Specifically, the licensee failed to evaluate extending the service life of safety-related molded case circuit breakers beyond the 20 year life expectancy, a condition adverse to quality. The licensee entered this issue into its corrective action program. The finding was more than minor in accordance with IMC 0612, Appendix B, Issue Screening, dated December 4, 2008, because the finding was associated with the Mitigating Systems Cornerstone attribute of equipment performance and affected the cornerstone objective to ensure the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences (i.e., core damage).Specifically, an unqualified safety-related molded case circuit breaker could lead to higher trip times and potential unavailability of safety-related components associated with the bus when a circuit fault is present. The finding screened as of very low safety significance because the finding was a qualification deficiency confirmed not to have resulted in loss of operability or functionality in service. This finding had a cross-cutting aspect in the area of Problem Identification and Resolution, operating experience, because the licensee failed to implement maintenance information through changes to station processes and procedures to address the qualification of the breakers from Vendor Technical Bulletin 06-2 (P.2(b)).m Vendor Technical Bulletin 06-2 (P.2(b)).  +
23:59:59, 30 September 2009  +
05000282  +  and 05000306  +
23:59:59, 30 September 2009  +
Has query"Has query" is a predefined property that represents meta information (in form of a <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Subobject">subobject</a>) about individual queries and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
Modification date"Modification date" is a predefined property that corresponds to the date of the last modification of a subject and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
00:39:28, 29 October 2017  +
23:59:59, 30 September 2009  +
Failure to Qualify Safety-Related Molded Case Circuit Breakers  +