A self-revealing NCV of 10 CFR 50, Appendi … A self-revealing NCV of 10 CFR 50, Appendix B, Criterion XVI was identified because the surveillance procedure frequency used to flush the service water (SW) piping in Mechanical Equipment Room (MER)-3 and MER-4 was changed from two weeks to four weeks without sufficiently considering the effects of river conditions on biological growth and without getting management permission to change the periodicity. As a result of the periodicity change, the B charging (CH) and main control room (MCR) SW header became blocked with biological growth and was declared inoperable on September 22, 2016, during the performance of 0-OSP-VS-012, High Flow Flush of SW Strainers and Piping in MER 3 and MER 4. As immediate corrective action, the licensee cleaned the clogged SW strainer and completed the backflushing of the SW header. The SW flushing periodicity was restored to a two week frequency to be seasonally and risk assessed and reduced as heavy fouling season ends. This issue was documented in the licensees corrective action program (CAP) as CR 1048251. The inspectors reviewed Inspection Manual Chapter (IMC) 0612, Appendix B, Issue Screening, dated September 7, 2012, and determined the performance deficiency (PD) was more than minor because it was associated with the equipment performance attribute of the Mitigating Systems Cornerstone, and it adversely affected the cornerstone objective to ensure the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. Using IMC 0609.04, Initial Characterization of Findings, Table 2, dated June 19, 2012, the finding was determined to affect the Mitigating Systems Cornerstone. The inspectors screened the finding using IMC 0609, Appendix A, Significance Determination Process (SDP) for Findings at-Power, dated June 19, 2012, and determined that it screened as Green because the deficiency did not affect the design or qualification of the charging pump service water pump system and it did not represent a loss of system safety function. This finding has a cross-cutting aspect in conservative bias aspect of the human performance area, H.14, because the licensee did not use decision making-practices that emphasize prudent choices over those that are simply allowed.hoices over those that are simply allowed.
23:59:59, 31 December 2016 +
23:59:59, 31 December 2016 +
Has query"Has query" is a predefined property that represents meta information (in form of a <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Subobject">subobject</a>) about individual queries and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
05000280/FIN-2016004-01 +, 05000280/FIN-2016004-01 +, 05000280/FIN-2016004-01 +, 05000280/FIN-2016004-01 +, 05000280/FIN-2016004-01 +, 05000280/FIN-2016004-01 +, 05000280/FIN-2016004-01 +, 05000280/FIN-2016004-01 +, 05000280/FIN-2016004-01 +, 05000280/FIN-2016004-01 +, 05000280/FIN-2016004-01 +, 05000280/FIN-2016004-01 +, 05000280/FIN-2016004-01 +, 05000280/FIN-2016004-01 +, 05000280/FIN-2016004-01 +, 05000280/FIN-2016004-01 +, 05000280/FIN-2016004-01 +, 05000280/FIN-2016004-01 +, 05000280/FIN-2016004-01 +, 05000280/FIN-2016004-01 +, 05000280/FIN-2016004-01 +, 05000280/FIN-2016004-01 +, 05000280/FIN-2016004-01 + and 05000280/FIN-2016004-01 +
Modification date"Modification date" is a predefined property that corresponds to the date of the last modification of a subject and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
12:56:21, 25 September 2017 +
23:59:59, 31 December 2016 +
Change of Surveillance Frequency Caused the Charging Service Water Header to Become Biologically Fouled +