Browse wiki

Jump to navigation Jump to search
The inspectors identified a Green NCV of tThe inspectors identified a Green NCV of the Surry operating license, section 3.I Fire Protection, for an inadequate procedure that resulted in compensatory continuous fire watches in MERs #3 and #4 being inadequate (CR 342078). This finding is greater than minor because it is associated with the reactor safety mitigating systems cornerstone attribute to provide protection against external events and adversely affects the cornerstone objective to ensure the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. The inspectors used Manual Chapter 0609, Appendix F, Fire Protection Significance Determination Process, to analyze this finding because the condition had an adverse affect on the Fixed Fire Protection Systems element of fire watches posted as a compensatory measure for fixed fire protection system outages or degradations. A low degradation rating was assigned to this finding as the provision affected by this finding (i.e. fire watches) is expected to display nearly the same level of effectiveness and reliability. Using Manual Chapter 0609, Appendix F, this finding was determined to be of very low safety significance (Green). A cross-cutting element was not assigned to this finding because the most significant contributor to the performance deficiency is not reflective of current performancey is not reflective of current performance  +
23:59:59, 30 September 2009  +
05000280  +  and 05000281  +
23:59:59, 30 September 2009  +
Has query"Has query" is a predefined property that represents meta information (in form of a <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Subobject">subobject</a>) about individual queries and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
Modification date"Modification date" is a predefined property that corresponds to the date of the last modification of a subject and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
00:38:56, 29 October 2017  +
23:59:59, 30 September 2009  +
Inadequate compensatory measures for the impairment of fire detection systems  +