Browse wiki

Jump to navigation Jump to search
The inspectors identified a Green NCV of TThe inspectors identified a Green NCV of TS 6.8.1, Procedures and Programs, as described in Regulatory Guide (RG) 1.33, Revision 2, February 1978, when PSEG performed chiller water system maintenance activities that were not properly preplanned in accordance with documented instructions, resulting in multiple chiller system trips on both units. Specifically, PSEG maintenance procedure SC.MD-PM.CH-0001, ACME Chiller Compressor Inspection and Repair, did not incorporate documented instructions from the vendor technical document. PSEG performed an apparent cause evaluation (ACE) 70171934, and revised the maintenance procedure that included detailed vendor instructions. This finding was more than minor because it was associated with the equipment performance attribute of the Mitigating System cornerstone, and adversely affected the cornerstone objective to ensure the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. Specifically, failure to install the chiller evaporator gasket in accordance with written instructions from the vendor manual resulted in multiple chiller failures. Using IMC 0609, Attachment 4, Initial Characterization of Findings, and Exhibit 2 of IMC 0609, Appendix A, The Significance Determination Process for Findings At-Power, dated June 19, 2012, the inspectors determined that this finding was of very low safety significance (Green) because the finding was not a design or qualification deficiency, did not represent a loss of safety system function, did not represent the loss of function for any TS system, train, or component beyond the allowed TS outage time, and it did not represent an actual loss of function of any non TS trains of equipment designated as high safety significance in accordance with PSEGs maintenance rule program. This finding had a cross-cutting aspect in the area of Problem Identification and Resolution, Evaluation, in that licensees thoroughly evaluate issues to ensure that resolutions address causes and extent of conditions commensurate with their significance. Specifically, PSEG did not thoroughly evaluate chiller divider plate head gasket failures in 2012, such that the resolution addressed the inadequate maintenance procedure instructions.equate maintenance procedure instructions.  
23:59:59, 30 June 2015  +
05000272  +  and 05000311  +
23:59:59, 30 June 2015  +
Has query"Has query" is a predefined property that represents meta information (in form of a <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Subobject">subobject</a>) about individual queries and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
Modification date"Modification date" is a predefined property that corresponds to the date of the last modification of a subject and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
12:57:36, 25 September 2017  +
23:59:59, 30 June 2015  +
Inadequate Chiller Maintenance Procedure  +