A Green finding and associated Non-Cited VA Green finding and associated Non-Cited Violation (NCV) of Title 10 of the Code of Federal Regulations Part 50, Appendix B, Criterion III, Design Control, was identified by the inspectors for the licensees failure to ensure that applicable regulatory requirements and design basis, for structures, systems, and components, were translated into procedures. Specifically, the licensee failed to include the floor plugs on the 26 level of the primary auxiliary building as credited flood barriers in procedure NP 8.4.7, PBNP Flooding Program.procedure NP 8.4.7, PBNP Flooding Program.  +
23:59:59, 30 June 2018  +
05000266  +
23:59:59, 30 June 2018  +
Has query"Has query" is a predefined property that represents meta information (in form of a <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Subobject">subobject</a>) about individual queries and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
Modification date"Modification date" is a predefined property that corresponds to the date of the last modification of a subject and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
22:35:03, 10 September 2018  +
23:59:59, 30 June 2018  +
Primary Auxiliary Building Floor Plug Removal Creates Unanalyzed Flood Path  +