ENS 5426611 September 2019 03:10:00A lightning strike occurred at approximately 1502 CDT on 09/10/2019, and a resulting power surge damaged some of the security door card reader system equipment. However, this did not affect access to plant areas for personnel who were already within protected area. At 1830 on 09/10/2019, it was discovered that some of the oncoming night shift personnel could not access particular areas that required the use of security card readers. Extent of condition check at 1934 on 09/10/2019 determined that access to 1A and 3A Electric Board Rooms, which contain remote shutdown panels and Fire Safe Shutdown equipment. was prohibited for the night shift personnel. This condition is reportable under 10 CFR 50.72(b)(3)(ii)(B) - Any event or condition that results in the nuclear power plant being in an unanalyzed condition that significantly degrades plant safety. Access was restored to all plant areas at 2106 on 9/10/2019. No plant events occurred during the time frame that the 1A & 3A Electric Board Rooms inaccessible that would have required access to these areas. The NRC Resident Inspector has been notified.